INSTALLATION INSTRUCTION

WARNING: The Izar AC charging station must be installed by a licensed electrician in accordance
with instructions in this manual. Failure to do so may lead to death, injury or property damage which
shall be borne by the user.
NOTE: Read this part carefully before working and install as instructed.
A. Plug-in installation (SEA 240/40I-U-6/6W/6Y and SEA 240/40I-U-14/14W/14Y)
1. Purchase outlet according to the model of Izar, 6-50R for SEA
240/40I-U-6/6W/6Y and 14-50R for SEA 240/40I-U-14/14W/14Y. If the
charger is installed outdoors, an anti-corrosion outlet is needed. And the
outlet should be equipped with a high-level waterproof box to ensure there is
no chance for water to get inside and thus lead to electroshock.
WARNING: Improper connection of the equipment-grounding conductor is able to result in a risk of electric shock.
Check with a qualified electrician or serviceman if you are in doubt as to whether the product is properly grounded. Do
not modify the plug provided with the product - if it will not fit the outlet, have a proper outlet installed by a qualified
electrician.
2. Choose the spec. of outlets' cable. Recommended: UL STW 2P*6AWG + 1PE*8AWG.
WARNING: Do not cut off or remove the plug of Izar (SEA 240/40I-U-6/6W/6Y and SEA 240/40I-U-14/14W/14Y) and
install it with hard-wired method, as this can void the even distribution of stress and waterproof function that Izar is
originally equipped with after production. Failure to follow this warning can lead to electroshock or death, and the
consequence and risk shall be borne by the user.
3. According to local regulation, ensure the main electrical panel supports a voltage as high as 240V
and to avoid fire risks, install Izar AC charging station only into circuits that are equipped with
overcurrent protection for branch circuits. The trip value of the branch circuit breaker for SEA
240/40I-U-6/6W/6Y and SEA 240/40I-U-14/14W/14Y should be 50A.
4. For plug-in installation, the NEMA outlet should be 31-1/2~33-15/32 inches (800~850mm) from
the ground in normal, and 23-5/8~25-19/32 inches (600~650mm) for the disabled. Ensure the outlet
is at a proper position that allows the plug to plug in easily.
NOTE:
1. GFCI breaker is not suggested as there is Charging
Circuit Interruption Device (CCID) protection inside
the Izar AC charging station. If GFCI breaker is used
in the upstream, tripping may frequently occur.
2. According to UL Standard for Safety Electric
Vehicle Supply Equipment, the plug input cable
length is about 11-13/16 inches (300mm). Ensure the
outlet is at a proper position that allows the plug to
plug in easily.
5. Adhere to all applicable regulations and install the
charger only with electrical permission.