B. Hard-wire (SEA 240/48I-U-H/HW/HY) installation
WARNING: The Izar AC charging station must be installed by a licensed electrician in accordance
with instructions in this manual. Failure to do so may lead to death, injury or property damage which
shall be borne by the user.
NOTE: Read this part carefully before working and install as instructed.
1. According to local regulation, ensure the main electrical panel supports a voltage as high as 240V
and to avoid fire risks, install Izar AC charging station only into circuits that are equipped with
overcurrent protection for branch circuits. The trip value of the branch circuit breaker for SEA
240/48I-U-H/HW/HY should be 60A.
2. Purchase non-GFCI bipolar breakers with a capacity of 60 amps for SEA 240/48I-U-H/HW/HY.
And the breaker should be equipped with a waterproof box.
3. For hard-wire (SEA 240/48I-U-H/HW/HY) installation, the waterproof box should be
47-1/4~51-3/16 inches (1200~1300mm) from the ground and 39-3/8~43-5/16 inches
(1000~1100mm) for the disabled.
4. Adhere to all applicable regulations and install the charger only with electrical permission.
WARNING: Do not remove the 31-1/2 inches (0.8m) input power cable of the Izar (SEA 240/48I-U-H/HW/HY) and use
a longer one for hard-wired installation, as this can void the even distribution of stress and waterproof function that Izar
is originally equipped with after production. Failure to follow this warning can lead to electroshock or death, and the
consequence and risk shall be borne by the user.