  • Page 2 These technical specifications state a row of manufactured sizes and models of smoke extraction dampers - single (further only dampers) SEDS-L. It is valid for production, designing, ordering, delivery, maintenance and operation. 1. Description......................... 2. Design..........................3. Dimensions, weights......................11 4.
  • Page 3 • External Casing leakage min. class B, Internal leakage min. class 3 acc. to EN 1751 • Cycling test in class C acc. to EN 12101-8 • ES Certificate No. 1391-CPR-2020/0187 • Declaration of Perfomance No. PM/SEDS-L/01/20/2 • Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19c...
  • Page 4 Working conditions Dampers are designed for smoke exhaust piping systems with underpressure max. 1500 Pa or overpressure max. 500 Pa. Dampers are designed for maximum air velocity 12 m/s. Dampers are installed with the horizontal or vertical axis of the blades. Dampers are intended for installation on air ducts and in/onto the walls where in the case of wall installation, this wall with damper does not have fire resistance and therefore does not separate two fire compartments.
  • Page 5 AC/DC 24 V AC/DC 24 V AC 230 V Power voltage 50/60Hz 50/60Hz 50/60Hz Power consumption - in operation - in the end position 0,1 W 0,3 W 0,4 W Dimensioning 6 VA (Imax 8,2 A @ 5 ms) 6,5 VA (Imax 8.2 A @ 5 ms) 7 VA (Imax 4 A @ 5 ms) Protection class Degree of protection...
  • Page 6 AC/DC 24 V AC/DC 24 V AC 230 V Power voltage 50/60Hz 50/60Hz 50/60Hz Power consumption - in operation 2,5 W 3,5 W - in the end position 0,1 W 0,3 W 0,4 W Dimensioning 5 VA (Imax 8,2 A @ 5 ms) 5,5 VA (Imax 8.2 A @ 5 ms) 6 VA (Imax 4 A @ 5 ms) Protection class...
  • Page 7 AC/DC 24 V AC 230 V Power voltage 50/60Hz 50/60Hz Power consumption - in operation 12 W - in the end position 0,5 W 0,5 W Dimensioning 18 VA (Imax 8,2 A @ 5 ms) 15 VA (Imax 7,9 A @ 5 ms) Protection class Degree of protection IP 54...
  • Page 8 Design with the communication and power supply unit Design with communication and power supply device BKNE 230-24 and with actuator BEN (BEE, BE)-ST pro 24V. The BKNE 230-24 serves on the one hand as a decentralized network device for powering the actuator and on the other hand transmits the signal of the communication and control device BKSE 24-6.
  • Page 9 Communication and supply device Power voltage AC 230V 50/60Hz Power consumption 10 W (including actuator) Dimensioning 19 VA (including actuator) Protection class Ambient operation temperature -30°C … +50°C Storage temperature -40°C … +80°C Connection - network cable 1 m without plug - drive 6-pin plug, 3-pin plug - terminal blocks...
  • Page 10 Communication and control devices indicates operating condition and faults of flue dampers. These conditions can be signalled or transmitted to the higher-level control system via the auxiliary built-in contacts. Signals from individual BKNE 230-24 are evaluated separately. All BKNE 230-24 are controlled simultaneously.
  • Page 11 Dimensions * standard height of the flange [mm] [mm] BEN / BEE 176,5 186,5 Damper body BEN / BEE + BKNE 236,5 Damper blade BE + BKNE 251,5 Actuating mechanism cover...
  • Page 12 Weights and effective area cross section 14.3 0.0227 17.6 0.0511 16.4 0.0270 20.3 0.0608 17.3 0.0350 21.5 0.0788 18.3 0.0430 22.6 0.0968 19.2 0.0510 23.8 0.1148 21.2 0.0554 26.4 0.1246 22.2 0.0634 27.6 0.1426 24.1 0.0794 30.0 0.1786 27.0 0.0917 33.7 0.2063 28.9...
  • Page 13 0.8832 90.0 1.1913 ³ ³ Example, how to calculate effective area and size of SEDS-L damper [AxB], when knowing air volume in [m /s] or [m /h] on damper. Maximum allowed air velocity on SEDS-L is 12 [m/s]. Formula: ³...
  • Page 14: Installation Examples

    Installation examples Pozice: Damper hinge Washer Profile C Washer C Wall construction without fire resistance Atypical protection box with access to actuator from side, not as standard from the top...
  • Page 15 Mounting to the ceiling wall Position: ² Threaded rod M8 – M20 36,6 Washer 84,3 Coupling Nut Anchor Hinge plate - min. thickness 10 mm Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm)
  • Page 16 Δp (Pa) Δp - static pressure drop w (m/s) w - air velocity in the free cross section (AxB) B - height of the damper B=200/400/600/800/1000/1200mm B=250mm B=300/450mm B=350/500/700/900/1100mm Sound power level corrected with filter A w - air velocity in the free cross section (AxB) - i.e. before blades f - frequency of octave band...
  • Page 17 w - air velocity in the free cross section (AxB) - i.e. before blades f - frequency of octave band w - air velocity in the free cross section (AxB) - i.e. before blades f - frequency of octave band...
  • Page 18 Damper casing and damper blade are made of galvanized plate without any other surface finish. Fasteners are galvanized. T he actuator cover is made of fire-resistant material (fire protection board) The appliance is constructed and preset by the manufacturer, its operation is dependent on proper installation and adjustment.
  • Page 19 Drill two holes into the protection box (from outside to inside) and pull through field wiring cables (fire resistant cables) to connect actuator trailing lead. Protection box is made of calcium silicate plates. Use drill (drill size acc. To suit connecting cable Ø + 2 mm for seal up by mastic) and make two holes (see fig.
  • Page 20 Spare parts are supplied only on basis of an order. Product label is placed on the damper casing MANDÍK, a.s. Dobříšská 550, 267 24 Hostomice, Czech Republic DIMENSION: ACTUATING SYSTEM: WEIGHT (kg): YEAR/SER.NO.: MANUAL FIRE PROTEC. CLASS: TPM 121/16 EN 12101-8:2011 Cert. No.: 1391-CPR-2020/0187, DoP: PM/SEDS-L/01/20/2 1391...
  • Page 21 technical specifications special design tab. 15.1.2 design according tab. 15.1.1 size type with actuating mechanism BEN, BEE, BE for 230V with actuating mechanism BEN, BEE, BE for 24V with actuating mechanism BEN (BEE)-SR for 24V .65* with the communication and supply device BKNE 230-24 and actuating mechanism BEN (BEE, BE)-ST for 24V insulation inside of the blades flanges with height 20 mm...
  • Page 22 MANDÍK, a.s. Dobříšská 550 26724 Hostomice Czech Republic Tel.: +420 311 706 706 E-Mail: mandik@mandik.cz www.mandik.com The producer reserves the right for innovations of the product. For actual product information see www.mandik.com...