Specifications - Omron ZEN-PA03024 Datasheet

Switching mode power supply
Table of Contents

Advertisement

Specifications

Ratings/Characteristics
Efficiency (typical)
Input
Voltage
Frequency
Current
Leakage current
Inrush current (See note 2.) 100 VAC input
Output
Voltage adjustment range (See note 3.)
Ripple
Input variation influence
Load variation influence (rated input voltage) 1.5% max.
Temperature variation influence
Start up time (See note 2.)
Hold time (See note 2.)
Additional
Overload protection (See note 2.)
functions
Parallel operation
Series operation
Others
Ambient temperature
Ambient humidity
Mounting method
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
EMI
Approved standards
Weight
Note: 1. This product has been approved for safety standards only when an AC input is used. It has not been approved when a DC input is used.
2. Refer to the Engineering Data section on page 4 for details.
3. If the V. ADJ adjuster is turned, the voltage will increase by more than 15% of the voltage adjustment range.
Check the output voltage of the power supply when converting the output voltage, and make sure that the load will not be damaged.
2
Switching Mode Power Supply
80% min.
100 to 240 VAC (85 to 264 VAC),
95 to 350 VDC (See note 1.)
50/60 Hz (47 to 450 Hz)
100 VAC input
0.8 A max.
200 VAC input
0.45 A max.
100 VAC input
0.4 mA max.
200 VAC input
0.75 mA max.
25 A max.
200 VAC input
50 A max.
- 10 to 15% (with V.ADJ) of rated output voltage
2% (p-p) max. ( - 25 to - 10 ° C: 4% max.)
0.5% max.
0.05%/ ° C max.
1,000 ms max. (100 VAC or 200 VAC, at rated output voltage)
15 ms min., 20 ms (typical) (100 VAC or 200 VAC, at rated output voltage)
105% to 135% of rated load current, inverted L drop, intermittent, automatic reset
Yes (2 units max. For details, refer to the derating curve in Engineering Data. For DC
input, parallel operation is possible only for 110 to 350 VDC.)
No
Operating: Refer to the derating curve in Engineering Data. (with no icing or conden-
sation)
Storage: - 25 to 75 ° C (with no icing or condensation)
Operating: 10 to 90%
Storage: 10 to 90%
DIN track mounting, surface mounting
2.0 kVAC for 1 min. (between all inputs and exposed non-current-carrying metal parts;
detection current: 10 mA max.)
3.0 kVAC for 1 min. (between all inputs and all outputs; detection current: 20 mA max.)
1.0 kVAC for 1 min. (between all outputs and non-current-carrying metal parts;
detection current: 10 mA max.)
100 M W min. (between all outputs and all inputs/exposed non-current-carrying metal
parts) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z direction
, 3 times each in ± X, ± Y, ± Z directions
2
300 m/s
Yes (color: green)
Conducted
Conforms to EN61000-6-3 (Class B)
emissions
Radiated
Conforms to EN61000-6-3 (Class B)
emissions
UL: UL508 Listing Class 2, 60950, 1604 (Class I/Division 2)
cUL: CSA C22.2 No. 14 Class 2, No. 60950, No. 213 (Class I/Division 2)
EN/VDE: EN60950 (=VDE0805), EN50178 (=VDE0160)
Conforms to VDE0106/P100 (Finger protection)
240 g max.
ZEN-PA03024

Advertisement

Table of Contents
loading

Table of Contents