Page 1
SD-076 PRODUCT: S8VS Power Supplies DATE: July 2013 TYPE: Partial Discontinuation Selected S8VS Switch Mode Power Supplies will be Discontinued June 2014; Use S8VS or S8VK Models Effective Date: Last orders due June, 2014 Affected Parts Product discontinuation Recommended replacement S8VS-01505 S8VK-G01505 S8VS-01512...
Wiring Diagram Product discontinuation Recommended replacement S8VS series S8VK-G series 60-W Models 120-W Models S8VK-G06024 S8VK-G12024 240-W Models S8VK-G24024 *1. The fuse is located on the (L) side. It is not user-replaceable. For a DC input, connect the positive voltage to the L terminal.
Page 6
Dimensions Product discontinuation Recommended replacement S8VS series S8VK-G series S8VK-G06024 (60 W) S8VK-G12024 (120 W) S8VK-G24024 (240 W)
Page 7
Specifications Item Product discontinuation Recommended replacement Model Model S8VS series Model S8VK-G series Model S8VK-C series Input voltage 100 to 240 VAC 100 to 240 VAC, (allowable range: 85 to 90 to 350 VDC, 264 VAC), 2-phase input from 3-phase source <240 VAC...
Page 8
Item Product discontinuation Recommended replacement Model Model S8VS series Model S8VK-G series Model S8VK-C series Conforms to EN61204-3 Conforms to EN61204- Conforms to (Radiated EN55011 Class B 3 EN55011 Class B EN61204-3, EN55011 Emissions) Class A Approved UL Listed: UL508 (Listing,...
Page 9
Operation Ratings Product discontinuation Recommended replacement S8VS series S8VK-GS series Derating Curve 240 W (S8VK-G24024) 120 W (S8VK-G12024) Note: 1. At less than 90 VAC, the Note: 1. At less than derating is 2.5%/V 90 VAC, the 2. For a DC power input, derating is 2.5%/V reduce the load given in 2.
Page 10
Safety Precautions for All Power Supplies Safety Precautions...
Page 11
List of Models Ordering Information @@@@@@...
Page 30
Buyer indemnifies Omron against all related costs or expenses. rights of another party. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery 16. Property; Confidentiality. Any intellectual property in the Products is the exclu-...
Page 32
New Product Switch Mode Power Supply S8VS (15/30/60/90/120/180/240/480-W Models) 60/90/120/180/240/480-W Models New Models with Indication Monitor and Simple Functions for Easy System Commissioning • New 90-W models with indication monitor that conform to UL Class 2 Output standards. • New models with screwless terminal blocks and indication monitor.
Page 33
With indication monitor (total run time monitor) With indication monitor but without alarm output (total run time monitor) Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
S8VS Ordering Information List of Models Note: For details on normal stock models, contact your nearest OMRON representative. Models without Indication Monitor (Standard Models) UL Class 2 Model number Model number Power ratings Input voltage Output voltage Output current Output standards...
Page 35
S8VS Specifications Ratings/Characteristics Power ratings 15 W 30 W Item Output voltage 12 V 24 V 12 V 24 V With 100-VAC input 74% typical 79% typical 83% typical 74% typical 81% typical 85% typical Efficiency With 200-VAC input 73% typical 78% typical 80% typical 74% typical...
Page 36
S8VS Power ratings 60 W 90 W Maintenance Total run time Maintenance Total run time Item Type Standard Standard forecast monitor monitor forecast monitor monitor With 100-VAC input 84% typical 83% typical 83% typical 83% typical Efficiency With 200-VAC input 83% typical 85% typical 84% typical 85% typical...
Page 37
S8VS Power ratings 120 W 180 W Maintenance Total run time Maintenance Total run time Item Type Standard Standard forecast monitor monitor forecast monitor monitor With 100-VAC input 84% typical 83% typical 85% typical 85% typical Efficiency With 200-VAC input 87% typical 85% typical 88% typical...
Page 38
S8VS Power ratings 240 W 480 W Maintenance Total run time Maintenance Total run time Item Type Standard Standard forecast monitor monitor forecast monitor monitor With 100-VAC input 85% typical 85% typical Efficiency With 200-VAC input 88% typical 89% typical Voltage *1 100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11) 100 to 240 VAC (allowable range: 85 to 264 VAC)
S8VS Connections Block Diagrams S8VS-015@@ (15 W) Undervoltage Fuse: 3.15 A indicator AC (L) INPUT Noise filter DC output −V AC (N) Inrush Rectifier/ Smoothing Rectifier current smoothing circuit protection circuit Drive control circuit Voltage detection circuit Overcurrent Overvoltage detection circuit detection circuit Photocoupler S8VS-030@@ (30 W)
Page 40
S8VS S8VS-06024A-@ (60 W) S8VS-06024B-@ (60 W) Display circuit Switch Arithmetic operation circuit Fuse Rectifier/smoothing circuit 6.3 A AC (L) INPUT Noise filter DC OUTPUT −V AC (N) Inrush Rectifier/ Rectifier/smoothing circuit Rectifier current smoothing protection circuit circuit Drive control Overcurrent Current detection circuit...
Page 41
S8VS S8VS-09024A@-@ (90 W) Sinking type S8VS-09024B@-@ (90 W) (S8VS-09024A-@, S8VS-09024B-@, S8VS-09024AS-@, S8VS-09024BS-@) S8VS-09024BE-@ (90 W) Sourcing type S8VS-09024A@S-@ (90 W) (S8VS-09024AP-@, S8VS-09024BP-@, S8VS-09024APS-@, S8VS-09024BPS-@) S8VS-09024B@S-@ (90 W) S8VS-09024BES-@ (90 W) Type with no alarm output (S8VS-09024BE-@, S8VS-09024BES-@) Display circuit Switch Alarm DC Low...
Page 42
S8VS S8VS-12024A@-@ (120 W) Sinking type S8VS-12024B@-@ (120 W) (S8VS-12024A-@, S8VS-12024B-@) Sourcing type S8VS-12024BE-@ (120 W) (S8VS-12024AP-@ S8VS-12024BP-@) Type with no alarm output (S8VS-12024BE-@) Switch Display circuit Alarm DC Low Arithmetic Yrs/kh operation circuit Common Rectifier/smoothing circuit Photocoupler Fuse 5.0 A AC (L) INPUT DC OUTPUT...
Page 43
S8VS S8VS-18024A@-@ (180 W) Sinking type (S8VS-18024A-@, S8VS-18024B-@) S8VS-18024B@-@ (180 W) Sourcing type S8VS-18024BE-@ (180 W) (S8VS-18024AP-@, S8VS-18024BP-@) Type with no alarm output (S8VS-18024BE-@) Switch Display circuit Alarm DC Low Arithmetic Yrs/kh operation circuit Common Rectifier/smoothing circuit Photocoupler Fuse 6.3 A AC (L) DC OUTPUT INPUT...
Page 44
S8VS S8VS-24024A@-@ (240 W) Sinking type (S8VS-24024A-@, S8VS-24024B-@) S8VS-24024B@-@ (240 W) Sourcing type S8VS-24024BE-@ (240 W) (S8VS-24024AP-@, S8VS-24024BP-@) Type with no alarm output (S8VS-24024BE-@) Display circuit Switch Alarm DC Low Arithmetic Yrs/kh operation circuit Common Rectifier/smoothing circuit Photocoupler Fuse 8.0 A AC (L) INPUT DC OUTPUT...
Page 45
S8VS S8VS-48024-@ (480 W) S8VS-48024A-@ (480 W) S8VS-48024B-@ (480 W) Fuse 12A AC (L) INPUT Noise filter DC OUTPUT −V AC (N) −V Inrush Rectifier/ Rectifier Harmonic current Smoothing smoothing circuit current suppression circuit −V protection (power factor circuit improvement) Overvoltage detection circuit Control...
Page 46
S8VS Construction and Nomenclature Nomenclature 15-W, 30-W Models S8VS-015@@/S8VS-030@@ Name Function Connect the input lines to these terminals. *1 Input terminals (L), (N) Connect the ground line to this terminal. *2 Protective Earth terminal (PE) DC Output terminals (−V), (+V) Connect the load lines to these terminals.
Page 47
S8VS Nomenclature 60-W Models Name Function Input terminals Connect the input lines to these Standard Model Models with Indication Monitor terminals. *1 (L), (N) S8VS-06024 S8VS-06024@ Protective Earth Connect the ground line to this terminal. *2 terminal (PE) DC Output terminals Connect the load lines to these (−V), (+V) terminals.
Page 48
S8VS 480-W Models Name Function AC Input terminals Connect the input lines to these Standard Model terminals. *1 (L), (N) S8VS-48024 Protective Earth Connect the ground line to this terminal. *2 terminal (PE) DC Output terminals Connect the load lines to these (−V), (+V) terminals.
S8VS Mounting Overload Protection 15 and 30 W The load and the power supply are automatically protected from overcurrent damage by this function. Overload protection is activated if the output current rises above Face-up mounting with DIN rail Standard mounting with DIN rail 105% of the rated current.
Page 51
S8VS Overvoltage Protection Undervoltage Alarm Function (Indication and Output) (S8VS-@@@24A@@/S8VS-@@@24B@@/ Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the S8VS-@@@24BE@ Only) feedback circuit in the Power Supply fails. If an excessive voltage that When output voltage drop is detected, an alarm ( ) and lowest is approximately 130% of the rated voltage (but approximately 110%...
Page 52
S8VS Dimensions Power Supplies with Screw Terminal Blocks Note: All units are in millimeters unless otherwise indicated. S8VS-015@@ (15 W) Five, M3.5 terminal S8VS-030@@ (30 W) screws with square 10.4 (Sliding: 10 max.) washers 35.2 10.2 (Sliding: 10 max.) 96.4 Rail stopper 22.5 Note: The illustration is the S8VS-03024 model.
S8VS Display and Alarm Output Functions and Operating Procedures S8VS-@@@24A@@ models (with display monitor) can display the output voltage, output current, peak hold current, or maintenance forecast monitor time. S8VS-@@@24B@@/S8VS-@@@24BE@ models (with display monitor) can display the output voltage, output current, peak hold current, or total run time.
Page 58
S8VS Peak Hold Current Reset Multiple Alarms The peak value of the output current (i.e., the peak hold current) can When two or more different alarms occur at the same time be reset on the display. Operation Mode Operation mode Key Press 3 seconds or more.
Page 59
S8VS Self-Diagnostics Function Numbers in the following table indicate the number used in Nomenclature on pages 15 and 17. Setting after (6) Main display Description Output status Restoration method restoration Noise detected in voltage or No change Automatic reset. No change current Maintenance forecast output...
Page 60
S8VS Maintenance Forecast (S8VS-@@@24A@@) Indication and Output When the Product is purchased, “ ” will be indicated. As Displays when the maintenance forecast has reached the set value. electrolytic capacitors deteriorate, indication changes to “ ” (Refer to page 30). “ ”...
Page 61
S8VS Maintenance Forecast Monitor Function The Power Supply is equipped with electrolytic capacitors. The maintenance forecast monitor function shows an approximate The electrolyte inside the electrolytic capacitor penetrates the sealing period left for maintenance of the Power Supply due to deterioration rubber and evaporates as time passes since it is manufactured, which of electrolytic capacitors.
Page 62
S8VS Models with Total Run Time Monitor Time Chart (S8VS-@@@24B@@/S8VS-@@@24BE@) Total run time S8VS-06024B 50 kh The accumulated value of the operating time of the Power Supply is displayed as the total run time. (kh) will be displayed initially after purchase and then the display will advance in 1-kh steps as the operating time accumulates.
S8VS Safety Precautions !CAUTION Minor electric shock, fire, or Product failure may Wiring occasionally occur. Do not disassemble, modify, or • Connect the ground completely. A protective earthing terminal repair the Product or touch the interior of the stipulated in safety standards is used. Electric shock or malfunction Product.
S8VS • Strip I/O wires for 11 mm when using a screwless terminal block. * The rated current for output terminals is 10 A per terminal. Be sure 60-, 90-, 120-, to use multiple terminals simultaneously for current that exceeds 180-, 240-W the terminal rating.
Page 65
S8VS Output Voltage Adjuster (V.ADJ) However, use the lower of the two maximum rated output currents as the current to the loads.) • The output voltage adjuster (V.ADJ) may possibly be damaged if it is turned with unnecessary force. Do not turn the adjuster with excessive force.
Page 66
S8VS • Type: Schottky barrier diode • Dielectric strength (V ): Rated Power Supply output voltage or higher • Forward current (I ): Twice the rated Power Supply output current or higher • Increase the output voltage setting of Power Supply A and Power Supply B by the drop in the forward voltage (V ) of diodes D1 and Also, the diodes will cause a power loss equivalent to the Power...
Page 68
Buyer indemnifies Omron against all related costs or expenses. rights of another party. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery 16. Property; Confidentiality. Any intellectual property in the Products is the exclu-...