Omron ZEN-PA03024 Datasheet
Omron ZEN-PA03024 Datasheet

Omron ZEN-PA03024 Datasheet

Switching mode power supply

Advertisement

Quick Links

Switching Mode Power Supply
ZEN-PA03024
Please read and understand this catalog before purchasing the prod-
ucts. Please consult your OMRON representative if your have any ques-
tions or comments. Refer to Warranty and Application Considerations
(page 8), and Safety Precautions (page 6)
New Compact Power Supply (30 W) for ZEN
Programmable Relays
• Slim size with a depth of 56 mm (W ´ H ´ D: 70 ´ 90 ´ 56 mm).
• EMI: Conforms to EN61000-6-3 (Class B).
• Allows parallel operation.
• Output voltage: 24 VDC; Output current: 1.3 A; Capacity: 30 W
• Safety standards: UL508/60950/1604,
CSA C22.2 No. 14/60950/213,
EN60950(VDE0806), EN50178(VDE0160)
• Uses lead-free soldering.
• Six-language instruction manual provided.
Model Number Structure
Model Number Legend
ZEN-PA 030 24
1
2
3
1. Unit
PA: Power supply unit
2. Power Ratings
030: 30 W
3. Output voltage
24: 24 V

Ordering Information

List of Models
Power ratings
30 W
100 to 240 VAC
Accessories (Order Separately)
Name
50 cm (l) ´ 7.3 mm (t)
Mounting Track
1 m (l) ´ 7.3 mm (t)
1 m (l) ´ 16 mm (t)
End Plate
Spacer
Input voltage
Output voltage
24 VDC
PFP-50N
PFP-100N
PFP-100N2
PFP-M
PFP-S
Switching Mode Power Supply
Output current
1.3 A
ZEN-PA03024
Models
ZEN-PA03024
Model number
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZEN-PA03024 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Omron ZEN-PA03024

  • Page 1: Ordering Information

    New Compact Power Supply (30 W) for ZEN Programmable Relays • Slim size with a depth of 56 mm (W ´ H ´ D: 70 ´ 90 ´ 56 mm). • EMI: Conforms to EN61000-6-3 (Class B). • Allows parallel operation.
  • Page 2: Specifications

    240 g max. Note: 1. This product has been approved for safety standards only when an AC input is used. It has not been approved when a DC input is used. 2. Refer to the Engineering Data section on page 4 for details.
  • Page 3: Block Diagram

    Current circuit detection circuit Overvoltage detection circuit Photocoupler Note: The Power Supply is provided with reinforced insulation between the input and output terminals. Installation Name Function AC input terminal (L1) Connect the input line to this termi- nal. A fuse is included in the cir- cuit.
  • Page 4: Engineering Data

    The Power Supply is provided with an overload protection function 85 to 264 VAC or 110 to 350 VDC input that protects the load and the power supply from possible damage by overcurrent. When the output current rises above 105% min. of the rated current, the protection function is triggered, decreasing the out- put voltage.
  • Page 5 35±0.3 27±0.15 35±0.3 25 15 15 25 25 * 15 25 1,000 1,000 (500) (See note.) Note: The values shown in parentheses are for the PFP-50N. End Plate Spacer PFP-M PFP-S 35.5 35.3 34.8 44.3 11.5 M4 x 8 pan head 16.5...
  • Page 6: Safety Precautions

    • Internal parts may occasionally deteriorate or be damaged. Store direction. the Power Supply at a temperature of - 25 to 65 ° C and a humidity of • Mounting Space 10% to 90%.
  • Page 7: Parallel Operation

    • Output voltage is adjustable with the output voltage adjuster Parallel Operation (V.ADJ) on the front surface of the product from - 10% to +15% of the rated output voltage. Two Power Supplies can be operated in parallel.
  • Page 8 CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE...