I/O Memory Allocation
Address
Words
Bits
A400
All
Error code
A401
A40103 Card
Transfer
Error Flag
A40105 Version
Error Flag
A40106 FALS Error
Flag (Fatal
error)
A40108 Cycle Time
Too Long
Flag
(Fatal error)
Name
When a non-fatal error
(user-defined FALS(006) or sys-
tem error) or a fatal error
(user-defined FALS(007) or sys-
tem error) occurs, the 4-digit
hexadecimal error code is written
to this word. When two or more
errors occur simultaneously, the
highest error code will be re-
corded.
Refer to the CS/CJ Series Op-
eration Manual for details on error
codes.
ON when the contents of the
memory card cannot be trans-
ferred to the CPU Unit at power
ON. (CJ2-series PLCs only)
ON when the transferred user
program contains a function that
is not supported by the unit ver-
sion of the CPU Unit. (CJ2-series
PLCs only)
ON when a non-fatal error is
generated by the FALS(006)
instruction. The CPU Unit will
continue operating and the
ERR/ALM indicator will flash.
The corresponding error code will
be written to A400. Error codes
C101 to C2FF correspond to
FALS numbers 001 to 511.
This flag will be turned OFF when
the FALS errors are cleared.
ON if the cycle time exceeds the
maximum cycle time set in the
PLC Setup (the cycle time moni-
toring time). CPU Unit operation
will stop and the ERR/ALM indi-
cator on the front of the CPU Unit
will light.
This flag will be turned OFF when
the error is cleared.
CS/CJ-series PLC
Function
CX-Simulator
Settings
Function
Error code
Same as
CS/CJ-series
PLC.
0: No error
Not used.
1: Error
Not used.
1:
Same as
FALS(006)
CS/CJ-series
executed
PLC.
0:
FALS(006)
not exe-
cuted
0: Cycle
Same as
time under
CS/CJ-series
max.
PLC.
1: Cycle
time over
max.
Section 9-3
Settings
219