Reference:
List of Commands
Designation
Parameter designation
Parameter confirmation ::END
Comment
Parameter output
RESET
Tag Name List
Classification
Parameter
Protocol
Baud Rate
Device ID
Time-out between
characters
Protocol time-out
Response time-out
Time-out between
blocks
Retry limit
Master/slave
SECS
Double block detec-
tion yes/no
Source ID
Single block No.
Operation
Baud rate for com-
munications with
Amplifier Unit/Link
Unit
Number of heads
count processing
ID Tag
Number of bytes in
the carrier ID
Segment name
Number of bytes in a
segment
Command input
(Tag name) = (Set value) <CRLF> Specify the parameter value corresponding to the tag name.
# (Comment) <CRLF> or CRLF
::GET_PARAM
::GET_SEG
::GET_E99SYS
::GET_VER
:EXIT
Tag name
S_BAUD
1200, 2400, 4800, 9600, 19200, 38400, 57600,
115200 bps
S_DEVID
0 to 32767
S_T1
0.1 to 10 s
S_T2
0.2 to 25 s
S_T3
1 to 120 s
S_T4
1 to 120 s
S_RTY
0 to 31
S_MS
M: Master
S: Slave
S_DB
1: The header of the block currently being received
is compared with the correct block received
immediately before, and double blocks are
detected.
0: Double block detection is not performed.
S_SRC
0 to 32767
S_BNO
0, 1
C_BAUD
9600, 19200, 38400 bps
Use a consistent baud rate setting within the same
system configuration.
C_HEAD
0 to 31
0:
1 to 31: The number of heads is specified. The
T_CIDLEN 16 (fixed)
T_SEGN
"S01" - "S99"
T_SEGL
8 (fixed)
Preparing for Communications
Explanation
Checks the parameter designations that have been received so
far and, if there is no error, confirms the settings.
This is ignored as the comment line.
Outputs the set parameters (protocol, SECS, operation).
Outputs the set parameters (ID Tag memory map).
Outputs the set parameters (operations).
Outputs the set parameters (software revision).
Restarts the CIDRW Controller.
Setting range
The number of heads is automatically
detected at the start. Any increase or
decrease in the number of heads is auto-
matically detected.
number of heads detected is compared
with this specified number of heads. If the
number of heads changes, for example
because a head fails, an error (with alarm)
is detected.
If a head is not connected or an error is
detected with a connected head, so that
the number of heads does not match the
specified number, an error (with alarm) is
detected.
SECTION 3
Default setting
9600 bps
0
0.5 s
10 s
45 s
45 s
3
M
0
0
1
9600 bps
0
16
"S01" - "S28"
8
CIDRW System
55
User's Manual