Omron GRT1 - 27-11-2006 Operation Manual page 41

Profibus communication unit
Table of Contents

Advertisement

Wiring the GRT1-PRT
Supplying I/O Power
Removing Wires
Recommended Power
Supplies
Recommended Wire
Strip Length
Pin Terminal Length
22
The power supply for I/O devices is supplied through the PROFIBUS Commu-
nication Unit's screwless clamping power supply terminals. If pin terminals are
used on the wire ends, the pin terminals can be inserted to wire the power.
These terminals supply power to the
external I/O devices connected to the
SmartSlice I/O Units.
Note
The GRT1-TBL Left Turnback Unit and GRT1-PD2 I/O Power Supply Unit
have the same screwless clamping power supply terminals. These terminals
are wired in the same way as the PROFIBUS Communication Unit's termi-
nals, by inserting the power supply wires.
To remove the wires press the release button above the terminal hole using a
slotted precision screwdriver and pull out the wire.
Slotted precision screwdriver
Release button
Use a SELV power supply with over current protection.
A SELV power supply has redundant or increased insulation between the I/O,
an output voltage of 30 Vr.m.s and a 42.4-V peak or maximum of 60 VDC.
Recommended power supply: S82K-01524 (OMRON) or S8TS-06024
(OMRON).
Type
Stranded wire
Solid wire
Pin terminal
Strip wire between 7 and 10 mm of insulation at the ends of the wires
(stranded or solid wire) or use pin terminals with a pin (conductor) length of 8
to 10 mm.
Strip 7 to 10 mm.
Release button
Holes for wires
Press the release button with
(pin terminals)
a screwdriver and pull out the
wire (pin terminal).
24 VDC
Side view
0.6 mm
Recommended model: SZF1 (Phoenix Contact)
Gauge
20 AWG to 16 AWG
2
(0.5 to 1.25 mm
)
Pin length: 8 to 10 mm