Omron CQM1H - 08-2005 Operation Manual page 124

Programmable controllers; inner boards
Hide thumbs Also See for CQM1H - 08-2005:
Table of Contents

Advertisement

Programming Devices
One-to-many
Communications
Serial
RS-232C cable at
communications
the personal
mode
computer
Host Link
Make your own
cable (See
below.)
Preparing RS-232C Cables
Connecting to
CX-Programmer
The following table shows the connections methods for communications
between one personal computer and many PCs.
RS-232C-to-
RS-422A/485 -
RS422A/485
to-RS-232C
Converting
Converting Link
Link Adapter
Adapter
3G2A9-
NT-AL001-E
AL004-E
Prepare the RS-232C cable between the 3G2A9-AL004-E Link Adapter and
the computer as shown below.
IBM PC/AT or compatible
Pin No.
---
RS-232C
interface
(D-sub, 9-pin, female)
The DIP switch settings of the NT-AL001-E Link Adapter are shown below.
When connecting the RS-232C port to the CX-Programmer, set the communi-
cations mode to Host Link mode and connect in the following way.
CQM1H-series CPU Unit
Signal
Pin No.
FG
1
SD
2
RD
3
RS-232C
RS
4
interface
CS
5
5V
6
DR
7
ER
8
SG
9
(D-sub, 9-pin, male)
When preparing an RS-232C cable to be connected to the RS-232C port, use
the following connector cables.
Connecting cable
Length
number
0.7 m
XW2Z-070T-1
2 m
XW2Z-200T-1
3G2A9-AL004-E Link Adapter
Pin No.
Signal
(D-sub, 25-pin, male)
Always ON
Turn ON at end of transmission path and turn OFF
elsewhere.
Turn both pins OFF for 4-wire connection.
Turn OFF pin 5 and turn ON pin 6 for RS-232C
CTS control.
Section 3-6
Port at PC
Model
RS-232C port
(D-Sub, 9-pin,
female)
Signal
RS-232C
interface
IBM PC/AT or compatible
Pin No.
Signal
1
CD
2
RD
3
SD
RS-232C
4
ER
interface
5
SG
6
DR
7
RS
8
CS
9
CI
(D-sub, 9-pin, female)
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents