Inverter Interface
5-4-2 Parameter Writing
Note 1
To write a 3G3MV parameter, the corresponding Inverter register must be
specified in the DM area specified by L (DM2023). Refer to the 3G3MV man-
ual for the Inverter register definitions.
A maximum number of 8 data items can be transferred in one operation.
Words
L+0
Number of data words including L (binary)
L+1
Transfer destination Inverter address (4 digits binary)
L+2
Number of transferred data items (4 digits binary)
L+3
Write data 1-1 (4 digits binary)
L+4
Write data 1-2 (4 digits binary)
L+5
...
L+6
...
L+7
...
L+8
...
L+9
...
L+10
...
Response data is stored in the DM area specified by K (DM2024).
In case of a normal completion:
Words
K+0
Number of data items (0002)
K+1
Normal response code (0000)
PLC Transfer Response Data Storage Destination; DM Area: K
Words
K+0
Number of data items (0002)
K+1
Error code (Note 1.)
For the error codes see section 5-4-7.
Function
Function
Function
SECTION 5
63