8.4 Environmental and safety
Standards
EMC (Emissions)
EMC (Immunity)
UPS enclosure IP rating
Earthing system
Operating temperature
Storage temperature
Relative humidity
Operating altitude
Audible noise
* For output cable < 10m.
*The load derating 1 % every up 100m @1000~3000m.
IEC62040-1:2008+A1:2013, EN IEC 62040-1: 2019+A11:2021
EN/IEC 62040-2 Electromagnetic Compatibility EMC (UPS EMC), category C2
IEC/EN 62040-3 Performance
CISPR32 Class A
IEC/EN 61000-3-2 Flickers
IEC/EN 61000-3-3 Harmonics
IEC 61000-4-2, (ESD): 4kV Contact Discharge / 8kV Air Discharge
IEC 61000-4-3, (Radiated field): 10V/m
IEC 61000-4-4, (EFT): 2kV
IEC 61000-4-5, (Surges): 1kV Differential Mode/2kV Common Mode
IEC 61000-4-6, (Electromagnetic field): 10V
IEC 61000-4-8, (Conducted magnetic field): 30A/m
IP20
This UPS can be connected to TN, TT, IT electrical supply system, same system is
supplied to the load
0 to 40 °C (32 to 104 °F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating
0 to 40 °C (32 to 104 °F) with batteries
-15 to 55 °C (5 to 130 °F) without batteries
0 to 95 % (without condensation)
Up to 3,000 meters (9,843 ft) above sea level, no derating for 40°c (104°F) room
temperature
< 50 dBA at 1 meter typical
37
9A UPS 1-3K