If the inverter is in the stop state, the load speed is displayed as the speed corresponding to the set
frequency, which is "set the load speed". Taking the set frequency 50.00Hz as an example, the load speed
in the stop state is: 50.00*2.000 = 100.00 (2 decimal places are displayed)
Accumulative
P7-13
power-on time
The cumulative power-on time of the inverter from the factory is displayed.
When this time reaches the set power-on time (P8-17), the output terminal (24) outputs an ON signal.
Accumulative power
P7-14
consumption
Displays the cumulative power consumption of the inverter

P8 Accessibility

P8-00
JOG running frequency 0.00Hz~Maximum frequency
P8-01
JOG acceleration time
P8-02
JOG deceleration time 0.0s~6500.0s
Define the given frequency and acceleration/deceleration time of the inverter when jogging. When jog
running, the start mode is fixed to the direct start mode (P 6-0 0 = 0), and the stop mode is fixed to the
deceleration stop (P6-10 = 0).
P8-03
Acceleration time 1
P8-04
Deceleration time 1
P8-05
Acceleration time 2
P8-06
Deceleration time 2
P8-07
Acceleration time 3
P8-08
Deceleration time 3
The inverter provides 4 sets of acceleration and deceleration time, which are P0-17\P0-18 and the
above three groups of acceleration and deceleration time.
The definitions of the four groups of acceleration and deceleration are exactly the same. Please refer
to the descriptions of P0-17 and P0-18. Through the different combinations of multi-function input
terminals, you can switch between 4 groups of acceleration/deceleration time, see P4-01~P4-05.
P8-09
Jump frequency 1 0.00Hz~Maximum frequency
P8-10
Jump frequency 2 0.00Hz~Maximum frequency
Frequency jump
P8-11
amplitude
When the set frequency is within the skip frequency range, the actual operating frequency will run at a
skip frequency that is closer to the set frequency. By setting the skip frequency, the inverter can be avoided
from the mechanical resonance point of the load.
Two skip frequency points can be set. If both skip frequencies are set to 0, the skip frequency function is
canceled. The principle of the hopping frequency and the hopping frequency amplitude is shown in Figure
6-16.
Chapter 6 Parameter Instruction
0h~65535h
0kW~65535
0.0s~6500.0s
0.0s~6500.0s
0.0s~6500.0s
0.0s~6500.0s
0.0s~6500.0s
0.0s~6500.0s
0.0s~6500.0s
0.00Hz~Maximum frequency
81
-
-
Default:2.00Hz
Default:20.0s
Default:20.0s
depend
depend
depend
depend
depend
depend
Default:0.00Hz
Default:0.00Hz
Default:0.01Hz