P5 Output Terminal - Veikong VFD200A Series Operation Manual

High performance vector frequency inverter
Table of Contents

Advertisement

AI is below the
P4-34
minimum input
setting selection
The function code is used when the voltage of the analog input is less than the set "minimum input",
and the corresponding setting of the analog quantity, the ones, tens, and hundred digits of the function code
respectively correspond to the analog input AI1. AI2, AI3.
If 0 is selected, when the AI input is lower than the minimum input, the corresponding setting of the
analog quantity is the minimum input corresponding setting (P4-14, P4-19, P4-24). If the selection is 1, the
analog input is set to 0.0% when the AI input is lower than the minimum input.
P4-35
Input terminal X1 delay time 0.0s~3600.0s
P4-36
Input terminal X2 delay time 0.0s~3600.0s
P4-37
Input terminal X3 delay time 0.0s~3600.0s
It is used to set the delay time for the inverter to change the state of the input terminal.
Currently only X1, X2, and X3 have the function of setting the delay time.
Input terminal
P4-38
valid
mode
selection 1
Input terminal
P4-39
valid
mode
selection 2
Used to set the active status mode of the digital input terminal.
0: Positive logic, the corresponding terminal is valid when connected to COM, and the disconnection
is invalid.
1: Inverse logic, the corresponding terminal is invalid when connected to COM, and the disconnection
is valid.

P5 Output terminal

The inverter comes standard with one multi-function analog output terminal, one multi-function
digital output terminal, one multi-function relay output terminal, and one FM terminal (optional as a
high-speed pulse output terminal, or as a collector open circuit) Switch output). If the above output
terminal does not meet the field application, you need to select the multi-function input and output
expansion card.
P5-00
Y2 output mode selection
Chapter 6 Parameter Instruction
Ones place: AI1 is lower than the minimum input setting
selection
0: corresponding to the minimum input setting
1:0.0%
Tens place: AI2 is lower than the minimum input setting
selection, the same as hundreds: AI3 is lower than the
minimum input setting selection, ibid.
Ones place: X1
Hundreds place: X3
Ten thousand: X6
0: The X terminal is connected to COM and the
disconnection is invalid.
1: X terminal and COM connection are invalid, the
disconnection is valid.
Ones place:X5
Hundreds place:X8
0: The X terminal is connected to COM and the
disconnection is invalid.
1: X terminal and COM connection are invalid, the
disconnection is valid.
0: Pulse output
Tens place: X2
Thousands place: X4
Tens place:X7
Thousands place:X9
1: Switch output
70
Default:000
Default:0.0s
Default:0.0s
Default:0.0s
Default:00000
Default:00000
Default:1