Operation And Maintenance; Overview; Calibration - Emerson Rosemount 3051S Manual

Electronic remote sensor system
Hide thumbs Also See for Rosemount 3051S:
Table of Contents

Advertisement

Reference Manual
00809-0100-4804
4 

Operation and maintenance

4.1 

Overview

This section contains information on commissioning and operating a 3051S Electronic
Remote Sensor (ERS) System.
Instructions for performing operation and maintenance functions are given for a
communication device. For convenience, communication device Fast Key sequences are
labeled "Fast Keys" for each software function below the appropriate headings.
Example software function
Fast Keys
4.2 

Calibration

4.2.1 
Calibration overview
Calibrating a Rosemount ERS System involves the following tasks:
Procedure
1. Configure process variables.
2. Calibrate the P
3. Zero trim the differential pressure.
4. Calibrate the 4–20 mA output.
4.2.2 
P
HI
P
Sensor
HI
P
Sensor
LO
www.emerson.com
1, 2, 3, etc.
See
Basic setup
for additional details on configuring the following:
Units of measure
Damping
Variable mapping
4 and 20 mA range points
Alarm and saturation levels
and P
HI
LO
Calibrate each pressure sensor by performing a zero/lower and an upper sensor
trim.
Perform a zero-trim on the Differential Pressure (DP) reading to establish a zero-
based measurement.
Adjust the analog output to match the control loop.
and P
sensor calibration
LO
3, 4, 3, 1
3, 4, 4, 1
pressure sensors.
Operation and maintenance
March 2024
55