Fluidwell D Series User Manual

Temperature indicator with high / low temperature alarms
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

Quick Links

User Manual
D043-A
TEMPERATURE INDICATOR
WITH HIGH / LOW TEMPERATURE ALARMS
Signal input:
(0)4-20 mA sensor signal
Signal output:
one temperature alarm
Options:
backlight
D-Series - Panel mounted indicators
More info: www.fluidwell.com/dseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell D Series

  • Page 1 User Manual D043-A TEMPERATURE INDICATOR WITH HIGH / LOW TEMPERATURE ALARMS Signal input: (0)4-20 mA sensor signal Signal output: one temperature alarm Options: backlight D-Series - Panel mounted indicators More info: www.fluidwell.com/dseries...
  • Page 2: Table Of Contents

    User Manual D043-A TABLE OF CONTENTS ABOUT THIS MANUAL......................How to use this manual ....................Use of pictograms ......................Warranty and technical support ..................Model Reference ......................SAFETY ............................ Personal safety ....................... End-user responsibilities....................Potential equipment damage ..................Disposal of electronic waste ................... INTRODUCTION........................
  • Page 3 D043-A User Manual MAINTENANCE........................27 General directions......................27 Instructions for repair ...................... 27 Battery replacement......................28 7.3.1 Safety instructions ......................28 7.3.2 Battery replacement procedure ..................28 7.3.3 Disposal of batteries ....................... 29 APPENDIX A - TECHNICAL SPECIFICATION ................30 General ...........................
  • Page 4: About This Manual

    ● incorrect functioning of the unit or connected instruments. A note informs you of important information. WARRANTY AND TECHNICAL SUPPORT For warranty and technical support on your Fluidwell products, visit our internet site www.fluidwell.com or contact us at support@fluidwell.com. MODEL REFERENCE Hardware version: 03.04.xx...
  • Page 5: Safety

    D043-A User Manual SAFETY PERSONAL SAFETY ● Risk of electric shock: Only open the unit if all leads are free of potential electrical energy. ● Immediately inform the person responsible for the installation if you disagree with the safety precautions or if you detect errors or danger. END-USER RESPONSIBILITIES ●...
  • Page 6: Introduction

    User Manual D043-A INTRODUCTION SYSTEM DESCRIPTION The temperature monitor model D043-A is a microprocessor-driven instrument designed to show the actual temperature, as well as to generate high and/or low temperature alarms. Fig. 1: The D043 This manual describes the daily use, configuration and installation of the D043-A with analog (0)4-20mA input from a temperature sensor, and its available options.
  • Page 7: Installation Example

    D043-A User Manual Input ● One temperature sensor with a passive or active (0)4-20mA analog signal output ● Several options are available for powering the sensor. Output ● An external device such as an alarm or a switch can be connected to the D043-A. ●...
  • Page 8: Operation

    User Manual D043-A OPERATION This unit may only be operated by authorized and trained personnel who have read and understood this manual, particularly Section 2: Safety [»5] INTRODUCTION This chapter describes the daily use and operation of the D043-A. For this, the D-Series is equipped with a control panel that provides the operator with various functions, information and operating modes.
  • Page 9: Backlight (Type Zb)

    D043-A User Manual Normally, the display is updated depending on the refresh rate selected in the configuration settings. By pressing any key, the display switches to refreshing the information 8 times per second. After 30 seconds of key inactivity, the display returns to the configured refresh rate. Fig. 4: Example of display information during process 4.2.2...
  • Page 10: Range Error

    User Manual D043-A 4.5.2 RANGE ERROR When the input value is more than 5% outside the calibrated measurement range, ALARM will be displayed, together with the calibrated value. After pressing the ▲ key, “LO RANGE” or “HI RANGE” will be displayed, indicating the reason for the alarm. 4.5.3 LOW BATTERY When the battery voltage drops, it must be replaced.
  • Page 11: Configuration

    D043-A User Manual CONFIGURATION INTRODUCTION This chapter describes how technicians can use configuration settings to configure the D-Series for optimal functionality. Configuration of the D043-A can be done in SETUP mode, using the front keys. CONFIGURING USING SETUP MODE For an overview of Operating modes, see Section 4.1.1: Operating modes [»8] Changing settings may influence current operation In SETUP mode the unit remains fully operational.
  • Page 12: Changing Configuration Settings

    User Manual D043-A 5.2.3 CHANGING CONFIGURATION SETTINGS A menu item either contains a value (a number with optionally a decimal point and sign, e.g. -123.45) or a selection list (e.g. L – m - USGAL). After a menu item is selected in the SETUP menu, a new value can be programmed by performing the following steps.
  • Page 13: Setup Menu Overview

    D043-A User Manual SETUP MENU OVERVIEW TEMPERATURE DEFAULT UNIT °C, °F, K, no unit °C DECIMALS 0 - 5 0.0010 - 999,999 1600 SPAN OFFSET -999,999 to +999,999 ALARM DEFAULT TEMPERATURE default - no relays - ignore default ZERO -999,999 to +999,999 ALARM LOW ALARM HIGH -999,999 to +999,999...
  • Page 14: Menu 2: Alarm

    User Manual D043-A TEMPERATURE UNIT Determines the measurement unit for the displayed temperature. The following can be selected: °C, °F, K, no unit Changing the measurement unit will have consequences for operator and setup values. Please note that the Span should be checked also. Recalculation is not done automatically.
  • Page 15: Menu 4: Power Management

    D043-A User Manual DISPLAY Display backlight is only available with Type ZB. The following functions will affect this optional backlight. BACKLIGHT With this setting, the optional backlight can be turned on or off. BACKLIGHT ALARM If the D043-A generates an alarm, the backlight can be set to change to red.
  • Page 16: Menu 5: Sensor

    User Manual D043-A 5.4.5 MENU 5: SENSOR SENSOR FILTER The analog output signal of a temperature sensor mirrors the actual process value. This signal is sampled several times per second by the D043-A. Consequently, random and/or fast changes in sensor signal may lead to instable displayed process values.
  • Page 17: Menu 6: Others

    D043-A User Manual SENSOR CALIBRATE HIGH The unit is calibrated in factory using a very accurate current source. In case the sensor signal does not equal 20mA at maximum temperature, this function is needed to set the input current at maximum temperature. Be very sure that the offered tuning signal is stable and correct before using it for calibration, since this setting has major influence on the accuracy of the system.
  • Page 18: Installation

    User Manual D043-A INSTALLATION ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 19: Handling The D043-A Enclosure

    D043-A User Manual HANDLING THE D043-A ENCLOSURE 6.2.1 IDENTIFICATION Identification label To identify your D043-A device, all enclosures have a weatherproof identification label placed at the backside of the product. Fig. 8: Example of D0-Series identification label Serial number and year of production The serial number can be reviewed on the identification label, the installation label, or in .
  • Page 20: Mounting The D-Series

    User Manual D043-A 6.3.2 MOUNTING THE D-SERIES The D-Series unit is mounted by placing it in an opening in a panel or cabinet (see Section 6.3.1: ) and securing it. To ensure proper IP or TYPE rating, the panel should Mechanical dimensions [»19] be rigid with a flat surface.
  • Page 21: Electrical Safety

    D043-A User Manual 6.4.1 ELECTRICAL SAFETY First consult the table with limiting environmental conditions and safety parameters in Section 6.1: Installation / environmental conditions [»18] General remarks ● Please note that the D043-A that came with a power module type PM will carry 110V-230V AC when installed.
  • Page 22: Field Wiring Connections

    User Manual D043-A 6.4.3 FIELD WIRING CONNECTIONS ● Do ground the aluminum / stainless steel enclosure properly with a PE wire as indicated to the Protective Earth terminal. It is the responsibility of the installer to install, connect and test the Protective Earth connections in accordance with the local and (inter)national Rules and Regulations.
  • Page 23: Terminal Connectors

    D043-A User Manual Jumper setting External sensor supply voltage 8.2 V DC 12 V DC 24 V DC TERMINAL CONNECTORS Take notice of all safety and precautionary measures indicated in Section 6.4: Electrical and review installation [»20] Section 6.4.3: Field wiring connections [»22] Section 6.4.4: Power before applying any field or power supply wiring.
  • Page 24: Terminals R1-R2 (R3): Output

    User Manual D043-A To power the D043-A a 24 V AC (Type PD) or 115-230 V AC (mains) (Type PM) power supply can be applied. P0 is connected to common ground, connect line (phase) to P1, and neutral (0) to P2. P2 N Type PD: 24 V AC Type...
  • Page 25: Terminals S1-S2 (S4): Temperature Sensor Input

    D043-A User Manual R2 and R3: Max 2 A @ 250 V AC / 30 V DC R3 R R2 R Device Device R1 Common Fig. 17: Terminals R1-R3: Mechanical relay output (type OR) 6.5.3 TERMINALS S1-S2 (S4): TEMPERATURE SENSOR INPUT The D043-A requires a (0)4-20mA temperature sensor signal which will be processed 4 times per second with 16 bit accuracy.
  • Page 26 User Manual D043-A Do not connect an AC (P1-P2) and a DC source (P3-P4) at the same time! Optional battery – Type PB With Type PB your product is equipped with a long-life Lithium primary battery. The battery will power the D043 when external power is not available. Page 26 FW_D043-A_M_v0501-01_EN...
  • Page 27: Maintenance

    D043-A User Manual MAINTENANCE GENERAL DIRECTIONS ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 28: Battery Replacement

    à plus de 100°C (212°F) ou exposer à l'eau. Primary Lithium Battery - Only replace with Fluidwell recommended battery pack! Pile primaire au lithium - Remplacer uniquement par une pile recommandé par Fluidwell! Fig. 20: Marking battery type PB: Safe area StdLiBAT-021 (SPB02) 7.3.2...
  • Page 29: Disposal Of Batteries

    D043-A User Manual 4. Place the back side cover back on the product and secure it with the four screws. 5. Check that the battery is installed properly by checking that the screen has come on. 6. Reconnect the unplugged field connectors. 7.
  • Page 30: Appendix A - Technical Specification

    User Manual D043-A APPENDIX A - TECHNICAL SPECIFICATION GENERAL DISPLAY Type High intensity reflective numeric and alphanumeric LCD, UV-resistant Digits 7 with height 17mm (0.67”) and 11 with height 8mm (0.31”). Various symbols and measuring units. Dimensions 90 x 40 mm (3.5” x 1.6”) Refresh rate User definable: fast - 1 sec - 3 sec - 15 sec - 30 sec - off Type ZB (option)
  • Page 31: Input

    D043-A User Manual INPUT TEMPERATURE SENSOR Signal type (0)4-20 mA, with signal calibration feature. Type PL min. 4 mA. Accuracy 16 bit. Error < 0.01 mA or ±0.05% FS. Low-level cut-off programmable. Span 0.0010 - 999,999 with variable decimal position. Offset -999,999 to +999,999 Update time...
  • Page 32: Appendix B - Troubleshooting

    User Manual D043-A APPENDIX B - TROUBLESHOOTING Table 1 lists and describes how to troubleshoot problems that can occur when installing or operating the D043-A. Table 2 lists internal alarm codes and conditions signaled by a blinking ALARM flag on the display ).
  • Page 33: Appendix C - Legal Information

    EU De cla tio n of Conformi Fluidwell 0 D ‒Series indicators he , February 2022 We, Fluidwell BV, declare under our s e ol respons ibility that the 0 D ‒Series indicators are de igne d and will operate conform the following applicable European...
  • Page 34 User Manual D043-A LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE: DATE: TEMPERATURE UNIT °C DECIMALS SPAN 1600 OFFSET ALARM TEMPERATURE default ZERO ALARM LOW ALARM HIGH DELAY ALARM LOW DELAY ALARM HIGH ALARM OUTPUT both DISPLAY SET ALARM operator BACKLIGHT BACKLIGHT ALARM BACKLIGHT BRIGHTNESS...
  • Page 35 D043-A User Manual NOTES FW_D043-A_M_v0501-01_EN Page 35...
  • Page 36 Fluidwell bv P.O. Box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives the Netherlands the Netherlands © Copyright 2024 - FW_D043-A_M_v0501-01_EN...