Fluidwell D Series User Manual

Flow rate monitor / totalizer with high / low flow rate alarms
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

Quick Links

User Manual
D013-A
FLOW RATE MONITOR / TOTALIZER
WITH HIGH / LOW FLOW RATE ALARMS
Signal input:
(0)4-20 mA flowmeter signal
Signal output:
one flow rate alarm
Options:
backlight
D-Series - Panel mounted indicators
More info: www.fluidwell.com/dseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell D Series

  • Page 1 User Manual D013-A FLOW RATE MONITOR / TOTALIZER WITH HIGH / LOW FLOW RATE ALARMS Signal input: (0)4-20 mA flowmeter signal Signal output: one flow rate alarm Options: backlight D-Series - Panel mounted indicators More info: www.fluidwell.com/dseries...
  • Page 2: Table Of Contents

    User Manual D013-A TABLE OF CONTENTS ABOUT THIS MANUAL......................How to use this manual ....................Use of pictograms ......................Warranty and technical support ..................Model Reference ......................SAFETY ............................ Personal safety ....................... End-user responsibilities....................Potential equipment damage ..................Disposal of electronic waste ................... INTRODUCTION........................
  • Page 3 D013-A User Manual Terminal connectors ....................... 24 6.5.1 Terminals P0-P2: AC power supply - Type PD or PM ............ 24 6.5.2 Terminals R1-R2 (R3): Output..................25 6.5.3 Terminals S1-S2 (S4): flowmeter input................26 6.5.4 Terminals P3-P4: DC power supply - Type PX, PD and Type ZB ........26 MAINTENANCE........................
  • Page 4: About This Manual

    ● incorrect functioning of the unit or connected instruments. A note informs you of important information. WARRANTY AND TECHNICAL SUPPORT For warranty and technical support on your Fluidwell products, visit our internet site www.fluidwell.com or contact us at support@fluidwell.com. MODEL REFERENCE Hardware version: 03.04.xx...
  • Page 5: Safety

    D013-A User Manual SAFETY PERSONAL SAFETY ● Risk of electric shock: Only open the unit if all leads are free of potential electrical energy. ● Immediately inform the person responsible for the installation if you disagree with the safety precautions or if you detect errors or danger. END-USER RESPONSIBILITIES ●...
  • Page 6: Introduction

    User Manual D013-A INTRODUCTION SYSTEM DESCRIPTION The flow rate monitor / totalizer model D013-A is a microprocessor-driven instrument designed to show the current flow rate, resettable total and non-resettable accumulated total, as well as to monitor the flow rate for high and/or low values. Fig. 1: The D013 This manual describes the daily use, configuration and installation of the D013-A with analog...
  • Page 7: Installation Example

    D013-A User Manual Input ● One flowmeter with a passive or active (0)4-20mA analog signal output ● Several options are available for powering the sensor. Output ● An external device such as an alarm or a switch can be connected to the D013-A. ●...
  • Page 8: Operation

    User Manual D013-A OPERATION This unit may only be operated by authorized and trained personnel who have read and understood this manual, particularly Section 2: Safety [»5] INTRODUCTION This chapter describes the daily use and operation of the D013-A. For this, the D-Series is equipped with a control panel that provides the operator with various functions, information and operating modes.
  • Page 9: Backlight (Type Zb)

    D013-A User Manual Normally, the display is updated depending on the refresh rate selected in the configuration settings. By pressing any key, the display switches to refreshing the information 8 times per second. After 30 seconds of key inactivity, the display returns to the configured refresh rate. TOTAL RATE Fig. 4:...
  • Page 10: Operator Alarms

    User Manual D013-A PROGRAM Fig. 5: Example of display information during programming minimum flow rate alarm level When a value was changed but ENTER has not been pressed, the change can be canceled by waiting for 20 seconds or by pressing ENTER and holding for three seconds. OPERATOR ALARMS 4.5.1 FLOW RATE ALARM...
  • Page 11: Configuration

    D013-A User Manual CONFIGURATION INTRODUCTION This chapter describes how technicians can use configuration settings to configure the D-Series for optimal functionality. Configuration of the D013-A can be done in SETUP mode, using the front keys. CONFIGURING USING SETUP MODE For an overview of Operating modes, see Section 4.1.1: Operating modes [»8] Changing settings may influence current operation In SETUP mode the unit remains fully operational.
  • Page 12: Changing Configuration Settings

    User Manual D013-A 5.2.3 CHANGING CONFIGURATION SETTINGS A menu item either contains a value (a number with optionally a decimal point and sign, e.g. -123.45) or a selection list (e.g. L – m - USGAL). After a menu item is selected in the SETUP menu, a new value can be programmed by performing the following steps.
  • Page 13: Setup Menu Overview

    D013-A User Manual SETUP MENU OVERVIEW TOTAL DEFAULT UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit DECIMALS 0 - 3 0.0010 - 999,999 1600 SPAN DECIMALS SPAN 0 - 6 FLOW RATE DEFAULT UNIT mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV -...
  • Page 14: Setup Menu Explanations

    User Manual D013-A SETUP MENU EXPLANATIONS 5.4.1 MENU 1: TOTAL Calculating the Span for Total The Span is used to convert the flowmeter output current to a quantity. The basis is the flow rate per second at 20 mA signal. Two examples are given. Example 1 ●...
  • Page 15: Menu 3: Alarm

    D013-A User Manual Example 1 ● The flowmeter generates 20 mA at a flow rate of 2,481.3 Liter/minute. ● The flow will be displayed using L/min ( 2.1: FLOW RATE > UNIT 2.2: FLOW RATE > TIME UNIT ● Thus, the span is 2481.3. ●...
  • Page 16: Menu 4: Display

    User Manual D013-A ALARM ALARM OUTPUT One output is available to transmit the alarm condition. With this setting the type of alarm to be transmitted can be set: low alarms, high alarms or both alarms. 5.4.4 MENU 4: DISPLAY DISPLAY FUNCTION Determines which information is shown on the main screen.
  • Page 17: Menu 6: Flowmeter

    D013-A User Manual 5.4.6 MENU 6: FLOWMETER FLOWMETER FORMULA The D013-A can process the analog (0)4-20mA signal in two ways: linear or as a root. Interpolation: the signal is processed in a linear way ● R = S x I Square root: the signal is processed applying a square root, f.i.
  • Page 18: Menu 7: Others

    User Manual D013-A FLOWMETER CALIBRATE LOW The unit is calibrated in factory using a very accurate current source. In case the flowmeter signal does not equal (0)4mA at flow rate zero, this function is needed to set the minimum input current at flow rate zero. The input loop powered version of the D013-A (Type PL) requires an input signal of at least 4 mA, not lower.
  • Page 19: Installation

    D013-A User Manual INSTALLATION ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 20: Handling The D013-A Enclosure

    User Manual D013-A HANDLING THE D013-A ENCLOSURE 6.2.1 IDENTIFICATION Identification label To identify your D013-A device, all enclosures have a weatherproof identification label placed at the backside of the product. Fig. 8: Example of D0-Series identification label Serial number and year of production The serial number can be reviewed on the identification label, the installation label, or in .
  • Page 21: Mounting The D-Series

    D013-A User Manual 6.3.2 MOUNTING THE D-SERIES The D-Series unit is mounted by placing it in an opening in a panel or cabinet (see Section 6.3.1: ) and securing it. To ensure proper IP or TYPE rating, the panel should Mechanical dimensions [»20] be rigid with a flat surface.
  • Page 22: Electrical Safety

    User Manual D013-A 6.4.1 ELECTRICAL SAFETY First consult the table with limiting environmental conditions and safety parameters in Section 6.1: Installation / environmental conditions [»19] General remarks ● Please note that the D013-A that came with a power module type PM will carry 110V-230V AC when installed.
  • Page 23: Field Wiring Connections

    D013-A User Manual 6.4.3 FIELD WIRING CONNECTIONS ● Do ground the aluminum / stainless steel enclosure properly with a PE wire as indicated to the Protective Earth terminal. It is the responsibility of the installer to install, connect and test the Protective Earth connections in accordance with the local and (inter)national Rules and Regulations.
  • Page 24: Terminal Connectors

    User Manual D013-A Jumper setting External sensor supply voltage 8.2 V DC 12 V DC 24 V DC TERMINAL CONNECTORS Take notice of all safety and precautionary measures indicated in Section 6.4: Electrical and review installation [»21] Section 6.4.3: Field wiring connections [»23] Section 6.4.4: Power before applying any field or power supply wiring.
  • Page 25: Terminals R1-R2 (R3): Output

    D013-A User Manual To power the D013-A a 24 V AC (Type PD) or 115-230 V AC (mains) (Type PM) power supply can be applied. P0 is connected to common ground, connect line (phase) to P1, and neutral (0) to P2. P2 N Type PD: 24 V AC Type...
  • Page 26: Terminals S1-S2 (S4): Flowmeter Input

    User Manual D013-A R2 and R3: Max 2 A @ 250 V AC / 30 V DC R3 R R2 R Device Device R1 Common Fig. 17: Terminals R1-R3: Mechanical relay output (type OR) 6.5.3 TERMINALS S1-S2 (S4): FLOWMETER INPUT The D013-A requires a (0)4-20mA flowmeter signal which will be processed 4 times per second with 16 bit accuracy.
  • Page 27 D013-A User Manual Do not connect an AC (P1-P2) and a DC source (P3-P4) at the same time! Optional battery – Type PB With Type PB your product is equipped with a long-life Lithium primary battery. The battery will power the D013 when external power is not available. FW_D013-A_M_v0501-01_EN Page 27...
  • Page 28: Maintenance

    User Manual D013-A MAINTENANCE GENERAL DIRECTIONS ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 29: Battery Replacement

    à plus de 100°C (212°F) ou exposer à l'eau. Primary Lithium Battery - Only replace with Fluidwell recommended battery pack! Pile primaire au lithium - Remplacer uniquement par une pile recommandé par Fluidwell! Fig. 20: Marking battery type PB: Safe area StdLiBAT-021 (SPB02) 7.3.2...
  • Page 30: Disposal Of Batteries

    User Manual D013-A 4. Place the back side cover back on the product and secure it with the four screws. 5. Check that the battery is installed properly by checking that the screen has come on. 6. Reconnect the unplugged field connectors. 7.
  • Page 31: Appendix A - Technical Specification

    D013-A User Manual APPENDIX A - TECHNICAL SPECIFICATION GENERAL DISPLAY Type High intensity reflective numeric and alphanumeric LCD, UV-resistant Digits 7 with height 17mm (0.67”) and 11 with height 8mm (0.31”). Various symbols and measuring units. Dimensions 90 x 40 mm (3.5” x 1.6”) Refresh rate User definable: fast - 1 sec - 3 sec - 15 sec - 30 sec - off Type ZB (option)
  • Page 32: Input

    User Manual D013-A INPUT FLOWMETER Signal type (0)4-20 mA, with signal calibration feature. Type PL min. 4 mA. Accuracy 16 bit. Error < 0.01 mA or ±0.05% FS. Low-level cut-off programmable. Span 0.0010 - 199,999 with variable decimal position. Update time Four times per second Voltage drop Max 1 V DC @ 20 mA.
  • Page 33: Appendix B - Troubleshooting

    D013-A User Manual APPENDIX B - TROUBLESHOOTING Table 1 lists and describes how to troubleshoot problems that can occur when installing or operating the D013-A. Table 2 lists internal alarm codes and conditions signaled by a blinking ALARM flag on the display ).
  • Page 34: Appendix C - Legal Information

    EU De cla tio n of Conformi Fluidwell 0 D ‒Series indicators he , February 2022 We, Fluidwell BV, declare under our s e ol respons ibility that the 0 D ‒Series indicators are de igne d and will operate conform the following applicable European...
  • Page 35 D013-A User Manual LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE: DATE: TOTAL UNIT DECIMALS SPAN 1600 DECIMALS SPAN FLOW RATE UNIT TIME UNIT DECIMALS SPAN 1600 DECIMALS SPAN ALARM FLOWZERO default ALARM LOW ALARM HIGH DELAY ALARM LOW DELAY ALARM HIGH ALARM OUTPUT both DISPLAY...
  • Page 36 Fluidwell bv P.O. Box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives the Netherlands the Netherlands © Copyright 2024 - FW_D013-A_M_v0501-01_EN...