Level monitor with linearization and high / low level alarms, signal input: 0 4-20 ma sensor signal, signal output: one level alarm, options: backlight (40 pages)
User Manual D012-P TABLE OF CONTENTS ABOUT THIS MANUAL......................How to use this manual ....................Use of pictograms ......................Warranty and technical support ..................Model Reference ......................SAFETY ............................ Personal safety ....................... End-user responsibilities....................Potential equipment damage ..................Disposal of electronic waste ................... INTRODUCTION........................
Page 3
D012-P User Manual Instructions for repair ...................... 28 Battery replacement......................29 7.3.1 Safety instructions ......................29 7.3.2 Battery replacement procedure ..................29 7.3.3 Disposal of batteries ....................... 30 APPENDIX A - TECHNICAL SPECIFICATION ................31 General ........................... 31 Input ..........................32 Operational ........................
● incorrect functioning of the unit or connected instruments. A note informs you of important information. WARRANTY AND TECHNICAL SUPPORT For warranty and technical support on your Fluidwell products, visit our internet site www.fluidwell.com or contact us at support@fluidwell.com. MODEL REFERENCE Hardware version: 03.04.xx...
D012-P User Manual SAFETY PERSONAL SAFETY ● Risk of electric shock: Only open the unit if all leads are free of potential electrical energy. ● Immediately inform the person responsible for the installation if you disagree with the safety precautions or if you detect errors or danger. END-USER RESPONSIBILITIES ●...
User Manual D012-P INTRODUCTION SYSTEM DESCRIPTION The flow rate indicator / totalizer model D012-P is a microprocessor-driven instrument designed to show the current flow rate, resettable total and non-resettable accumulated total. Fig. 1: The D012 This manual describes the daily use, configuration and installation of the D012-P with pulse input from a flowmeter and its available options.
D012-P User Manual INSTALLATION EXAMPLE Following parts can be recognized in below installation example. Fig. 3: Installation example D012-P 1. Front cover 3. Label 5. Keys 7. Clamp 2. Display 4. Protective earth 6. Mounting panel 8. Back side cover connection FW_D012-P_M_v0501-01_EN Page 7...
User Manual D012-P OPERATION This unit may only be operated by authorized and trained personnel who have read and understood this manual, particularly Section 2: Safety [»5] INTRODUCTION This chapter describes the daily use and operation of the D012-P. For this, the D-Series is equipped with a control panel that provides the operator with various functions, information and operating modes.
D012-P User Manual Normally, the display is updated depending on the refresh rate selected in the configuration settings. By pressing any key, the display switches to refreshing the information 8 times per second. After 30 seconds of key inactivity, the display returns to the configured refresh rate. TOTAL RATE Fig. 4:...
User Manual D012-P 4.4.2 INTERNAL ERROR When an internal error occurs, “ALARM” will be displayed. Press the SELECT key several times to display the 4-digit error code. Consult for more information. Section B: Troubleshooting [»33] Page 10 FW_D012-P_M_v0501-01_EN...
D012-P User Manual CONFIGURATION INTRODUCTION This chapter describes how technicians can use configuration settings to configure the D-Series for optimal functionality. Configuration of the D012-P can be done in SETUP mode, using the front keys. CONFIGURING USING SETUP MODE For an overview of Operating modes, see Section 4.1.1: Operating modes [»8] Changing settings may influence current operation In SETUP mode the unit remains fully operational.
User Manual D012-P 5.2.3 CHANGING CONFIGURATION SETTINGS A menu item either contains a value (a number with optionally a decimal point and sign, e.g. -123.45) or a selection list (e.g. L – m - USGAL). After a menu item is selected in the SETUP menu, a new value can be programmed by performing the following steps.
D012-P User Manual SETUP MENU OVERVIEW TOTAL DEFAULT UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit DECIMALS 0 - 3 0.000010 - 9,999,999 K-FACTOR DECIMALS K-FACTOR 0 - 6 FLOW RATE DEFAULT UNIT mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV -...
User Manual D012-P When a different unit is selected, the displayed values are NOT recalculated. TOTAL UNIT Determines the measurement unit for total and accumulated total. The following units can be selected: L - m3 - kg - lb - GAL - USGAL - bbl - no unit Changing the measurement unit will have consequences for operator and setup values.
D012-P User Manual FLOW RATE UNIT Determines the measurement unit for the flow rate. The following can be selected: mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV - no unit - scf - Nm3 - NL - P Changing the measurement unit will have consequences for operator and setup values.
User Manual D012-P 5.4.4 MENU 4: POWER MANAGEMENT POWER MANAGEMENT LCD UPDATE Sets the LCD display refresh rate. The following can be selected: fast - 1 sec - 3 sec - 15 sec - 30 sec - off When a key is pressed, the display refresh rate will switch to ‘fast’ for 30 seconds.
D012-P User Manual 5.4.6 MENU 6: OTHERS OTHERS TYPE / MODEL Provides important information on your product. This information may be SOFTWARE VERSION required for maintenance or support. SERIAL NUMBER PASS CODE All SETUP values can be password protected. A four-digit password can be programmed, for example 1234. To disable password protection, enter four zeros (0000).
User Manual D012-P INSTALLATION ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
D012-P User Manual HANDLING THE D012-P ENCLOSURE 6.2.1 IDENTIFICATION Identification label To identify your D012-P device, all enclosures have a weatherproof identification label placed at the backside of the product. Fig. 7: Example of D0-Series identification label Serial number and year of production The serial number can be reviewed on the identification label, the installation label, or in .
User Manual D012-P 6.3.2 MOUNTING THE D-SERIES The D-Series unit is mounted by placing it in an opening in a panel or cabinet (see Section 6.3.1: ) and securing it. To ensure proper IP or TYPE rating, the panel should Mechanical dimensions [»19] be rigid with a flat surface.
D012-P User Manual 6.4.1 ELECTRICAL SAFETY First consult the table with limiting environmental conditions and safety parameters in Section 6.1: Installation / environmental conditions [»18] General remarks ● Please note that the D012-P that came with a power module type PM will carry 110V-230V AC when installed.
User Manual D012-P 6.4.3 FIELD WIRING CONNECTIONS ● Do ground the aluminum / stainless steel enclosure properly with a PE wire as indicated to the Protective Earth terminal. It is the responsibility of the installer to install, connect and test the Protective Earth connections in accordance with the local and (inter)national Rules and Regulations.
D012-P User Manual 8.2 V DC 12 V DC V - 1 V DC (~24 V DC) Fig. 11: Jumper positions sensor supply voltage selection (Type PD or PM) Jumper setting External sensor supply voltage 8.2 V DC 12 V DC 24 V DC Func TERMINAL CONNECTORS...
User Manual D012-P To power the D012-P a 24 V AC (Type PD) or 115-230 V AC (mains) (Type PM) power supply can be applied. P0 is connected to common ground, connect line (phase) to P1, and neutral (0) to P2. P2 N Type PD: 24 V AC Type...
Page 25
D012-P User Manual The D012-P is suitable for use with flowmeters with an NPN output signal. For reliable pulse detection, the pulse amplitude has to go below 1.2 V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency ( SETUP 5.1: FLOWMETER >...
User Manual D012-P Namur The D012-P is suitable for use with flowmeters with a NAMUR signal. Type PD or PM can power the sensor per terminal S4 (see Section 6.4.5: Sensor supply [»22] Type PD, PM: ensor supply NAMUR S2 Signal Shield 820 Ω...
Page 27
D012-P User Manual Optional battery – Type PB With Type PB your product is equipped with a long-life Lithium primary battery. The battery will power the D012 when external power is not available. FW_D012-P_M_v0501-01_EN Page 27...
User Manual D012-P MAINTENANCE GENERAL DIRECTIONS ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
à plus de 100°C (212°F) ou exposer à l'eau. Primary Lithium Battery - Only replace with Fluidwell recommended battery pack! Pile primaire au lithium - Remplacer uniquement par une pile recommandé par Fluidwell! Fig. 21: Marking battery type PB: Safe area StdLiBAT-021 (SPB02) 7.3.2...
User Manual D012-P 4. Place the back side cover back on the product and secure it with the four screws. 5. Check that the battery is installed properly by checking that the screen has come on. 6. Reconnect the unplugged field connectors. 7.
D012-P User Manual APPENDIX A - TECHNICAL SPECIFICATION GENERAL DISPLAY Type High intensity reflective numeric and alphanumeric LCD, UV-resistant Digits 7 with height 17mm (0.67”) and 11 with height 8mm (0.31”). Various symbols and measuring units. Dimensions 90 x 40 mm (3.5” x 1.6”) Refresh rate User definable: fast - 1 sec - 3 sec - 15 sec - 30 sec - off Type ZB (option)
User Manual D012-P DIRECTIVES AND STANDARDS EN/BS 61000-6-2 EN/BS 61000-6-3 EN/BS 61326-1 Low Voltage EN/BS 61010-1 RoHS EN/BS 50581 EN/BS IEC 63000 IP & NEMA EN/BS 60529 NEMA 250 Note See the applicable Declaration of Conformity or product certificate for specific revisions and publication dates of applicable standards.
D012-P User Manual APPENDIX B - TROUBLESHOOTING Table 1 lists and describes how to troubleshoot problems that can occur when installing or operating the D012-P. Table 2 lists internal alarm codes and conditions signaled by a blinking ALARM flag on the display ).
EU De cla tio n of Conformi Fluidwell 0 D ‒Series indicators he , February 2022 We, Fluidwell BV, declare under our s e ol respons ibility that the 0 D ‒Series indicators are de igne d and will operate conform the following applicable European...
Page 35
D012-P User Manual LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE: DATE: TOTAL UNIT DECIMALS K-FACTOR DECIMALS K-FACTOR FLOW RATE UNIT TIME UNIT DECIMALS K-FACTOR DECIMALS K-FACTOR CALCULATION CUT-OFF DISPLAY FUNCTION total BACKLIGHT BACKLIGHT BRIGHTNESS POWER MANAGEMENT LCD UPDATE 1 sec BATTERY MODE operational FLOWMETER...