Wine Guardian D088 Installation, Operation And Maintenance Manual page 39

Ducted self-contained wine cellar cooling systems
Table of Contents

Advertisement

Fan AUTO or
ON
Compressor
anti-short
cycling
Defrost
sensor
enable/disable
Defrost cut-in
temperature
Setting 7
• Press "Settings" button to advance to
Setting 7.
• Press the "Up" or "Down" arrow buttons
to adjust number to the desired set
point. Factory default is zero (0).
Zero (0) = Auto–fan only turns on when
there is a call for cooling or heating
One (1) = Fan On–fan remains on
continuously
Setting 8
• Press "Settings" button to advance to
Setting 8.
• Press the "Up" or "Down" arrow buttons
to adjust to the desired time in one-
minute increments. Maximum is 10
minutes; minimum is 3 minutes. Factory
default is 5 minutes.
Compressor anti-short cycling time is
the amount of allowable time between
compressor stop and restart. Rapid
start/stop of compressors can cause
premature failure.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER
THAN FACTORY DEFAULT.
Setting 9
• Press "Settings" button to advance to
Setting 9.
• Press the "Up" or "Down" arrow buttons
to adjust to the desired setpoint.
1 will equal enabled and a 0 (zero) will
equal disabled.
If the defrost setting is enabled when no
sensor is present the unit will display !3
which will shut off the system.
Setting 10
• Press "Settings" button to advance to
Setting 10.
• Press the "Up" or "Down" arrow buttons
to adjust to the desired setpoint. This
setting is adjustable from 25°F to 40°F.
Factory default is 39°F.
There must be at least a 1°F difference
between defrost cut-in and cut-out set
points.
39