5
Appendix
5.1

Differences from the standard inverter

The following functions/specifications of the FR-E800 standard model are changed in the FR-E800-HVC inverters.
Item
PU/EXT key on the operation panel
Plug-in option
Optional operation panel
Terminal PR
Terminals MRS and FU
Terminal RES
Terminals S1, S2, SO, and SOC
Terminal 4
Terminal FM
PU connector
Multiple rating
Load pattern selection
Estimated lifespan of parts
108
5. Appendix
5.1 Differences from the standard inverter
Changed to the HAND/AUTO key.
Cannot be used.
Cannot be used.
Not provided.
Brake resistors, high-duty brake resistors, brake units, resistor units, discharging resistors,
multifunction regeneration converters, and high-duty brake resistors cannot be used.
Not provided.
Not provided.
The initial value of Pr.184 is changed to "9999".
Refer to the FR-E800 Instruction Manual (Function).
Not provided.
"80, 81, 180, and 181" cannot be set in Pr.190 to Pr.192.
Refer to the FR-E800 Instruction Manual (Function).
Not provided.
Pr.126 cannot be set.
"20 and 21" cannot be set in Pr.128.
"4" cannot be set in Pr.178 to Pr.182, and Pr.185 to Pr.189.
"4, 5, 7, 10, 12, 16, 25, 62, 65 to 67" cannot be set in Pr.183 and Pr.184.
Pr.267 cannot be set.
"3" cannot be set in Pr.609.
"3" cannot be set in Pr.610, and the initial value is changed to "4".
The initial value and the setting range of Pr.804 are changed to "1".
"1" cannot be set in Pr.810.
"1 to 3" cannot be set in Pr.840.
Pr.846 to Pr.848, and Pr.858 cannot be set.
Pr.904, Pr.905, Pr.932, and Pr.933 cannot be set.
Refer to the FR-E800 Instruction Manual (Function).
Not provided.
Pr.54 and Pr.900 cannot be set.
Refer to the FR-E800 Instruction Manual (Function).
Not provided. (The RS-485 terminals (connector) are added.)
The setting range of Pr.550 is changed to "2 and 9999".
Refer to the FR-E800 Instruction Manual (Communication).
LD rating only.
Pr.570 cannot be set.
Refer to the FR-E800 Instruction Manual (Function).
The initial value of Pr.14 is changed to "1".
Refer to the FR-E800 Instruction Manual (Function).
8 years for cooling fan, main circuit smoothing capacitor, and on-board smoothing capacitor
Description