 Single-phase 200 V class
FR-E820S-0082(2.2K), 0017(0.4K)
R/L1 S/L2
Earthing
(grounding)
terminal
Power supply
NOTE
• Make sure the power cables are connected to the R/L1, S/L2, and T/L3. (Phase need not be matched.) Never connect the
power cable to the U, V, and W of the inverter. Doing so will damage the inverter.
• Connect the motor to U, V, and W. (The phases must be matched.)
 Handling of the wiring cover(FR-E820-0587(18.5K) or lower, FR-E840-0349(18.5K) or lower, FR-
E820S-0030(0.75K) or lower or lower)
1.
To prevent injury, wear protective equipment such as cut-resistant gloves.
2.
Place the wiring cover 2 securely on wooden blocks or the like to punch out knockout holes easily.
3.
To punch out the knockout holes in the wiring cover 2, use a go-through screwdriver and alternately tap the points
marked with black circles in the following figure repeatedly. Be careful not to put the screwdriver directly on the joints.
Remove any sharp edges and burrs from the knockout holes.
(Example) FR-E820-0082(2.2K)-HVC
Jumper
N/-
P/+
M
Motor
FR-E820S-0030(0.75K) to 0082(2.2K)
N/- P/+
Jumper
R/L1 S/L2
Earthing
(grounding)
terminal
Power supply
Go-through
screwdriver
M
Motor
Joints
43
2. Installation and Wiring