Peripheral Devices - Mitsubishi Electric FR-E800-HVC Series Instruction Manual

Table of Contents

Advertisement

2.1.2

Peripheral devices

Check the model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.
Refer to the following table for right selection.
 Molded case circuit breaker / earth leakage circuit breaker
• This is a matrix showing the rated current of the molded case circuit breaker (MCCB) or earth leakage circuit breaker (ELB)
(NF or NV type) according to the selected inverter and rating.
Voltage
Inverter model
FR-E820-0011(0.2K)
FR-E820-0017(0.4K)
FR-E820-0030(0.75K)
FR-E820-0051(1.1K)
FR-E820-0082(2.2K)
FR-E820-0102(3.0K)
Three-phase
FR-E820-0167(5.5K)
200 V class
FR-E820-0255(7.5K)
FR-E820-0340(11K)
FR-E820-0476(15K)
FR-E820-0587(18.5K)
FR-E820-0748(22K)
FR-E820-0978(30K)
FR-E840-0018(0.75K)
FR-E840-0030(1.5K)
FR-E840-0047(2.2K)
FR-E840-0059(3.0K)
FR-E840-0094(5.5K)
Three-phase
FR-E840-0149(7.5K)
400 V class
FR-E840-0196(11K)
FR-E840-0298(15K)
FR-E840-0349(18.5K)
FR-E840-0383(22K)
FR-E840-0510(30K)
FR-E820S-0011(0.2K)
FR-E820S-0017(0.4K)
Single-phase
FR-E820S-0030(0.75K)
200 V class
FR-E820S-0051(1.1K)
FR-E820S-0082(2.2K)
NOTE
• Select an MCCB according to the power supply capacity.
• Install one MCCB per inverter.
• For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the document enclosed with the product
and select appropriate fuses.
• When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cables and reactors according to the motor output.
• When the breaker installed on the inverter input side is shut off, check for the wiring fault (short circuit), damage to internal
parts of the inverter etc. The cause of the output shutoff must be identified and removed before turning ON the power of the
breaker.
22
2. Installation and Wiring
2.1 Peripheral devices
Without AC/DC power factor
improving reactor
5 A
5 A
10 A
15 A
20 A
30 A
40 A
60 A
75 A
125 A
150 A
175 A
225 A
5 A
10 A
10 A
20 A
30 A
40 A
50 A
75 A
100 A
100 A
125 A
5 A
10 A
15 A
20 A
40 A
MCCB
INV
M
MCCB
INV
M
With AC/DC power factor
improving reactor
5 A
5 A
5 A
10 A
15 A
20 A
30 A
50 A
60 A
100 A
125 A
125 A
175 A
5 A
10 A
10 A
15 A
20 A
30 A
40 A
50 A
60 A
75 A
100 A
5 A
10 A
10 A
20 A
30 A

Advertisement