Article number
Load resistance range
Output current
Output delay with resistive load
Parallel switching of two outputs
Switching frequency
Total current of the outputs
horizontal installation
vertical installation
Cable length
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA
•
lower limit
upper limit
•
•
for signal "1" rated value
•
for signal "0" residual current, max.
•
"0" to "1", typ.
•
"1" to "0", typ.
•
for uprating
•
for redundant control of a load
with resistive load, max.
•
•
with inductive load, max.
on lamp load, max.
•
•
Current per channel, max.
Current per module, max.
•
Total current of the outputs (per module)
–
up to 40 °C, max.
up to 50 °C, max.
–
–
up to 60 °C, max.
up to 30 °C, max.
–
–
up to 40 °C, max.
–
up to 50 °C, max.
•
shielded, max.
•
unshielded, max.
Isochronous mode
Execution and activation time (TCO), min.
Bus cycle time (TDP), min.
Jitter, max.
Interrupts/diagnostics/status information
Diagnostics function
Substitute values connectable
Technical specifications
7.1 Technical specifications
6ES7132-6BH00-0CA0
48 Ω
12 kΩ
0.5 A
0.1 mA
50 µs
100 µs
No
Yes
100 Hz
0.1 Hz
10 Hz
0.5 A
8 A
8 A
6 A
4 A
8 A
6 A
4 A
1 000 m
600 m
48 µs
500 µs
8 µs
Yes
Yes
37