Parameter data record
A.2 Error codes
Error code in STATUS parameter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B2
H
H
H
DF
80
E0
H
H
H
DF
80
E0
H
H
H
DF
80
E1
H
H
H
DF
80
E1
H
H
H
DF
80
E1
H
H
H
44
Meaning
00
Module not accessible.
H
01
Header error (version or specified bits incor­
H
rect).
02
Header error (number or length of paramet­
H
er structures or parameter blocks incorrect)
01
Reserved bit set.
H
02
Invalid diagnostics enable bit set for operat­
H
ing mode.
06
Invalid coding for substitute value behavior. Use valid code for "Reaction to CPU STOP"
H
Solution
Check station.
Plug the module in correctly.
Check parameters of the WRREC block.
Correct version number or fixed bits, see
Header information (Page 42).
Correct the number and length of the para­
meter structures or parameter blocks, see
Header information (Page 42).
Describe all reserved bits with 0.
Correct diagnostics enables. Dependence on
check for wire break parameter, see Struc­
ture of byte x to x+2 for channels 0 to
15 (Page 42-43).
parameter, see Structure of byte x to x+2 for
channels 0 to 15 (Page 42-43).
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA