Address Space - Siemens SIMATIC ET 200SP Equipment Manual

Digital output module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

5.3

Address space

The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image output/input.
Configuration options of DQ 16x24VDC/0.5A HF
You can configure the module with STEP 7 (TIA Portal) or with a GSD file. If you configure the
module by means of a GSD file, the configurations are available under various short
designations/module names; see the table below. The following configurations are possible:
Table 5-2  Configuration options with GSD file
Configuration
1 x 16-channel with value status
1 x 16-channel without value
status
1 x 16-channel with value status
for module-internal shared output
with up to 4 submodules
2 x 8-channel with value status
2 x 8-channel without value status DQ 16x24VDC/0.5A HF V1.0, S.2
4 x 4-channel with value status
4 x 4-channel without value status DQ 16x24VDC/0.5A HF V1.0, S.4
NOTE
The following functions are only fully available when the submodule X.1 is configured and
the IO controller to which submodule X.1 is assigned has established a connection to the IO
device.
• Firmware update
• I&M identification data
• PROFIenergy
2 x 8- / 4 x 4-channel configuration
For the configuration, the channels of the module are divided into multiple submodules.
These submodules can be assigned to different IO controllers when the module is used in a
Shared Device.
The number of usable submodules is dependent on the interface module used. Read the
information in the Equipment Manual for the respective interface module.
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA
Short designation/module
name in the GSD file
DQ 16x24VDC/0.5A HF V1.0, QI
DQ 16x24VDC/0.5A HF V1.0
DQ 16x24VDC/0.5A HF V1.0,
MSO
DQ 16x24VDC/0.5A HF V1.0, S.2
QI
DQ 16x24VDC/0.5A HF V1.0,
S.4, QI
Configuration software, e.g. with STEP 7 (TIA Portal)
Integrated in the
GSD file
STEP 7 hardware
PROFINET IO
catalog, as of V18
with HSP0416
X
X
X
X
X
X
X
Parameters/address space
5.3 Address space
GSD file
PROFIBUS DP
X
X
X
X
X
-
X
-
X
-
X
-
X
-
23