Siemens SIMATIC ET 200SP Equipment Manual page 20

Digital output module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
5.1 Parameters
Parameter
Channel activated
Reaction to CPU STOP
Potential group
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD configur­
1
ation, the parameter setting options are restricted. The parameter length of the I/O module is 14 bytes with a PROFIBUS
GSD configuration. However, if necessary you can set this parameter with data records 64 to 71 or data record 128, see
Appendix "Parameter data record".
NOTE
• If both parameters "Diagnostics: Short circuit to L+" and "Diagnostics: Wire break" are
enabled and one of these diagnostic events occurs, the affected channel is switched off.
This prevents undefined load switching and the corresponding diagnostics alarm is
triggered.
• If the parameter "Diagnostics: Wire break" is enabled and the parameter "Diagnostics:
Short circuit to L+" is disabled and a "Diagnostics: wire break" is pending, the affected
channel is switched off. This prevents undefined load switching and the corresponding
diagnostics alarm is triggered.
• If the parameter "Diagnostics: Short circuit to L+" is enabled and "Diagnostics: Wire break"
is disabled, the signal status is retained at the affected channel when "Diagnostics: Short
circuit to L+" occurs. A diagnostics alarm is triggered only for 0 signal.
20
Value range
Disable
Enable
Turn off
Keep last value
Output substitute value 1
Use the potential group of
the left module (module
plugged into a dark
BaseUnit)
Enable new potential group
(module plugged into a
light BaseUnit)
Default
Configuration
in RUN
Enable
Yes
Turn off
Yes
Use potential
No
group of the left
module
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA
Scope with configuration soft­
ware, e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Channel
Channel
Module
Module
Module