Technical specifications
7.1 Technical specifications
Article number
Address space per module
Automatic encoding
Submodules
Selection of BaseUnit for connection variants
Short-circuit protection
Switching capacity of the outputs
36
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption, max.
output voltage / header
Rated value (DC)
Power loss
Power loss, typ.
Address area
Address space per module, max.
•
Hardware configuration
•
Mechanical coding element
Type of mechanical coding element
•
•
Number of configurable submodules, max.
1-wire connection
•
•
2-wire connection
•
3-wire connection
Digital outputs
Type of digital output
Number of digital outputs
Current-sinking
Current-sourcing
Digital outputs, parameterizable
•
Response threshold, typ.
Limitation of inductive shutdown voltage to
Controlling a digital input
with resistive load, max.
•
•
with inductive load, max.
on lamp load, max.
•
6ES7132-6BH00-0CA0
24 V
19.2 V
28.8 V
Yes
20 mA; without load
24 V
1 W
8 byte
Yes
Yes
Type A
4
BU type A0
BU type A0 with AUX terminals or potential dis
tributor module
BU type A0 with AUX terminals or potential dis
tributor module
Source output (PNP, current-sourcing)
16
No
Yes
Yes
Yes; Electronic
0.7 to 1.3 A
Typ. L+ (-50 V)
Yes; digital output, according to IEC 61131-2,
type 0.5
0.5 A
0.5 A
5 W
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA