Technical specifications
7.1 Technical specifications
Maximum permitted switching frequency of inductive loads
The following trends show the maximum permissible switching frequency of inductive loads
as a function of inductance and channel current. The maximum switching frequency applies
to a pulse-pause ratio of 50%. The channel contributes 500 mA to the total current of the
module, even if the actual channel current is smaller.
If you do not know the inductance of the actuator, assume a maximum inductance of
1.152 H for DC-13 loads (IEC 60947-5-1).
Figure 7-2  Maximum switching frequency
Dimension drawing
See Equipment Manual ET 200SP BaseUnits
(https://support.industry.siemens.com/cs/ww/en/view/59753521)
40
100.00
10.00
1.00
0.10
10
5 mH
10 mH
30 mH
100
Rated current of the channel / mA
50 mH
100 mH
300 mH
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA
500 mH
1152 mH