Siemens SIMATIC ET 200SP Equipment Manual page 25

Digital output module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Address space for configuration as 1 x 16-channel DQ 16x24VDC/0.5A HF, MSO
For the configuration as a 1 x 16-channel module (module-internal Shared Output, MSO),
channels 0 to 15 of the module are copied to up to four submodules. Channels 0 to 15 are
then available with identical values in various submodules. These submodules can be
assigned to up to four IO controllers when the module is used in a shared device:
• The IO controller to which submodule 1 is assigned has write access to outputs 0 to 15.
• The IO controllers to which submodule 2, 3, or 4 is assigned have read access to outputs 0
to 15.
Value status (Quality Information, QI)
The meaning of the value status depends on the submodule on which it occurs.
With the 1st submodule (= basic submodule), the value status 0 indicates that the value is
incorrect or that the IO controller of the basic submodule is in STOP mode.
For the 2nd to 4th submodule (=MSO submodule), the value status 0 indicates that the value
is incorrect or one of the following errors has occurred:
• The basic submodule is not yet configured (not ready).
• The connection between the IO controller and the basic submodule has been interrupted.
• The IO controller of the basic submodule is in STOP or POWER OFF state.
Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
Equipment Manual, 01/2024, A5E52818470-AA
Parameters/address space
5.3 Address space
25