Section 5 - Technical data

Wiring diagram with ATS dual power disconnect

Notes
Description
1
Programming: per customer request.
2
Refer to the user manual for operation, connections
and tightening torque values.
3
The customer is required to provide branch circuit
protection and disconnecting means per NEC and local
code.
4
Dash lines indicate customer installed devices and
wiring.
5
Use copper conductors only. 75°C (167°F) rated or
higher; terminations rated for 75°C (167°F).
54
Notes
Description
6
Refer to the user's manual for I/O ratings.
7
Short circuit current rating 100KA RMS symmetrical, for
480V maximum.
8
Individual motor FLA; refer to the performance report.
9
Unit FLA; refer to the performance report.
10
Lineator (harmonic filter) - selectable option.
11
Automatic transfer switch - selectable option.
12
Fused disconnect - provided with ATS option.
Form CRAH102.20-N1
Issue date: 03/11/2024
Johnson Controls