York F2RP018 Installation Manual

York F2RP018 Installation Manual

Single piece air handlers

Advertisement

INSTALLATION
MANUAL

TABLE OF CONTENTS

GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
CONVERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUCT CONNECTORS . . . . . . . . . . . . . . . . . . . . . . . . . . 5
AIR FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SUSPENSION KITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
COIL METERING DEVICES . . . . . . . . . . . . . . . . . . . . . . 6
REFRIGERANT LINE CONNECTION . . . . . . . . . . . . . . . 7
LOW VOLTAGE CONTROL CONNECTION . . . . . . . . . . 8
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . 8
BLOWER SPEED CONNECTIONS . . . . . . . . . . . . . . . . 8
DRAIN CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . 19
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
COIL CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
LUBRICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
CONDENSATE DRAINS . . . . . . . . . . . . . . . . . . . . . . . . 19
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . 19
CAUTION:
READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
SINGLE PIECE AIR HANDLERS
HEAT PUMP MODELS
F2RP / F2FP018 THRU 060
F3RP / F3FP018 THRU 060
COOLING MODELS
F2RC / F2FC 024 THRU 036
035-14520-001 Rev. B (0803)

Advertisement

Table of Contents
loading

Summary of Contents for York F2RP018

  • Page 1: Table Of Contents

    INSTALLATION SINGLE PIECE AIR HANDLERS HEAT PUMP MODELS MANUAL F2RP / F2FP018 THRU 060 F3RP / F3FP018 THRU 060 COOLING MODELS F2RC / F2FC 024 THRU 036 TABLE OF CONTENTS GENERAL INFORMATION ..... . . 2 INSPECTION .
  • Page 2: General Information

    035-14520-001 Rev. B (0803) GENERAL INFORMATION REFERENCE This Single Piece Air Handler provides the flexibility for instal- Use this instruction in conjunction with the instructions for the lation in any upflow or horizontal application. These versatile appropriate indoor unit, air moving system and accessories. models may be used for cooling or heat pump operation with Installer should pay particular attention to the words NOTE, or without electric heat.
  • Page 3: Location

    035-14520-001 Rev. B (0803) LOCATION Condensate drain lines are connected in the front (clear of filter). Location is usually predetermined. Check with owner's or Filter removal. dealer's installation plans. If location has not been decided, consider the following in choosing a suitable location: When no electric heat is used, the unit as well as all duct work and plenum are designed for zero clear- Select a location with adequate structural support, space...
  • Page 4: Horizontal Drain Pan Installation / Conversion

    035-14520-001 Rev. B (0803) HORIZONTAL DRAIN PAN INSTALLATION / Horizontal drain cutout in the center access panel should be removed by using a utility knife (if not previously cut CONVERSION out). These air handler units are supplied ready to be installed in a right hand horizontal position when a horizontal pan is factory installed.
  • Page 5: Dimensions

    035-14520-001 Rev. B (0803) DIMENSIONS Dimensions Wiring K.O.’s* Refrigerant MODEL Connections F2RP /F2FP Line Size F3RP(T) /F3FP(T) F2RC/F2FC Height Width Depth Power Control Liquid Vapor 40-3/4 14-7/8 16-1/2 40-3/4 14-7/8 16-1/2 40-3/4 14-7/8 16-1/2 7/8 (1/2) 036(RC) 40-3/4 12-1/8 14-7/8 16-1/2 1-3/8 (1) 036(RP)
  • Page 6: Air Filters

    Air filters must be field supplied. A 1" filter access rack has Indoor Coil Model Metering Device been built into the unit. See Figure 4. Remove filter access F2RP018 / F2FP018 Orifice - 53 cover shown. Install proper size filter. Standard 1" size per- F2RP024 / F2FP024...
  • Page 7: Refrigerant Line Connection

    035-14520-001 Rev. B (0803) • If the suction line is 3/4" diameter - position the bulb A standard orifice is pre-installed in the unit and is marked on near the top of the copper tube as shown. If the tube is the unit data plate.
  • Page 8: Electric Heaters & Operating Controls

    035-14520-001 Rev. B (0803) Suction line connections are made outside the center For units with heaters with circuit breakers in a horizontal access panel. Cut off the suction line as close to the end right application, a label must be applied to the unit to as possible.
  • Page 9 035-14520-001 Rev. B (0803) ELECTRIC HEAT FAN RELAY CONNECTIONS WITHOUT CIRCUIT BREAKER SINGLE SOURCE (2.5 - 10 KW) TRANSFORMER GND. GND. CONNECTIONS (HIGH VOLTAGE) POWER 4-PIN POWER SUPPLY CONNECTOR ELECTRIC HEAT WITHOUT CIRCUIT BREAKER 3 PHASE (10 - 15 KW) GND.
  • Page 10 035-14520-001 Rev. B (0803) Table 2: PHYSICAL AND ELECTRICAL DATA Models F2RC/F2FC/F2RP/F2FP/F3RP(T) 036(RP/FP) 036(RC/FC) Blower - Diameter x Width 9 x 6 10 x 6 10 x 8 10 x 8 10 x 8 Motor Nominal RPM 1075 1075 1075 1075 1075 Voltage...
  • Page 11 035-14520-001 Rev. B (0803) Table 5: ELECTRICAL DATA - 1 Ø - 208/230-1-60 KW Staging** Max. Static Total Heat Models Heater* & Min. CFM F2RP/F3RP(T)/F2RC W1 Only W2 Only W1 + W2 Model F2FP/F3FP(T)/F2FC Static 208V 240V 208V 240V 208V 240V 208V 240V...
  • Page 12 035-14520-001 Rev. B (0803) Table 6: ELECTRICAL DATA - (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 1 Ø - 208/230-1-60 Field Wiring Models Heater Heater* Max. O.C.P. Amps/ F2RP/F3RP(T)/F2RC Amps Min. Circuit Ampacity 75°C Wire Size - AWG Model Type F2FP/F3FP(T)/F2FC 240V...
  • Page 13 035-14520-001 Rev. B (0803) Table 7: ELECTRICAL DATA - (FOR MULTI-SOURCE POWER SUPPLY) - COPPER WIRE 1 Ø - 208/230-1-60 Min. Circuit Ampacity Max. Time Delay Fuse 75°C Wire Size - AWG Models Heater Circuit Circuit Circuit F2RP/F3RP(T)/F2RC Model F2FP/F3FP(T)/F2FC 208/240 208/240 208/240...
  • Page 14 035-14520-001 Rev. B (0803) Table 10: ELECTRICAL DATA - 1 Ø - 220/240-1-50 KW Staging Max. Static Total Heat Heater Model & Min. CFM W1 Only W2 Only W1 + W2 Model Static 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V...
  • Page 15 035-14520-001 Rev. B (0803) Table 12: ELECTRICAL DATA - (FOR MULTI-SOURCE POWER SUPPLY) - COPPER WIRE 1 Ø - 220/240-1-50 THIS TABLE FOR SINGLE PHASE AIR HANDLERS WITH SINGLE PHASE HEATERS Min. Circuit Ampacity Max. Time Delay Fuse 75°C Wire Size - AWG Circuit Circuit Circuit...
  • Page 16 035-14520-001 Rev. B (0803) Table 15: AIR FLOW DATA - (HEAT PUMP MODELS) 230 Volt 208 Volt Models Blower F2RP/F2FP Motor @ External Static Pressure - IWG F3RP(T)/F3FP(T) Speed 0.10 0.20 0.30 0.40 0.50 0.10 0.20 0.30 0.40 0.50 High Med.
  • Page 17 035-14520-001 Rev. B (0803) Table 17: AIR FLOW DATA - (50 HZ MODELS) 240 Volt - 50 HZ Blower or M /H @ External Static Pressure - IWG or PA MODEL Motor 0.10 0.20 0.30 0.40 0.50 Speed High 1615 1547 1471 1420...
  • Page 18 035-14520-001 Rev. B (0803) COOLING ONLY COOLING WITH ELECTRIC HEAT THERMOSTAT THERMOSTAT OUTDOOR OUTDOOR UNIT UNIT COIL COIL G W2 W1 O G W2 W1 O UNIT UNIT * NOT REQUIRED ON 2 OR 5KW FIGURE 14 : Cooling Wiring HEAT PUMP OUTDOOR THERMOSTAT...
  • Page 19: Drain Connections

    035-14520-001 Rev. B (0803) DRAIN CONNECTIONS The drain pan connections are designed to ASTM Standard D 2466 Schedule 40. Use 3/4" PVC or steel threaded pipe. All drain lines should be trapped a minimum of three inches, Since the drains are not subject to any pressure it is not nec- should be pitched away from unit drain pan and should be no essary to use Schedule 40 pipe for drain lines.
  • Page 20 NOTES Subject to change without notice. Printed in U.S.A. 035-14520-001 Rev. B (0803) Copyright © by York International Corp. 2003. All rights reserved. Supersedes: 035-14520-001 Rev. A (0902) Unitary 5005 Norman Products York Group Drive 73069...