INSTALLATION MANUAL
MODULAR MULTI-POSITION
AIR HANDLERS
MODELS: ME SERIES
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
DUCT WORK AND CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . .5
ELECTRIC HEATER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .6
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
LOW VOLTAGE CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . .7
Return Air Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Coil and Air Handler Attachment Details . . . . . . . . . . . . . . . . . . . . . . .3
Gasket Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Typical Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Physical and Electrical Data - Cooling Only . . . . . . . . . . . . . . . . . . . . .8
Electrical Data - Cooling Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Electrical Heat: Minimum Fan Speed . . . . . . . . . . . . . . . . . . . . . . . . . .8
SECTION I: GENERAL
The MP modular air handler series provides the flexibility for installation
in any position. This unit may be used for upflow, downflow, horizontal
right, or horizontal left applications.
These units may be located in a closet, utility room, attic, crawl space,
or basement. These versatile models may be used for cooling or heat
pump operation with or without electric heat or indoor coil.
Top or side power and control wiring, color coded leads for control
wiring, and electric heaters all combine to make the installation easy
and minimize installation cost.
Electric heat kits are available as field installed accessories. Single
phase kits are available from 2.5 kW to 25 kW. 208-230 volt three
phase kits are available from 10kW to 25kW.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property
damage.
LIST OF SECTIONS
BLOWER SPEED CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 7
UNIT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
AIR SYSTEM ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
TYPICAL THERMOSTAT CONNECTIONS . . . . . . . . . . . . . . . . . . . 14
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
LIST OF FIGURES
Duct Work Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Blower Speed Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical Thermostat Wiring Diagram - ECM . . . . . . . . . . . . . . . . . . . 14
Wiring Diagram - Three Phase Heat Kits . . . . . . . . . . . . . . . . . . . . . 16
LIST OF TABLES
Air Flow Data (CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. A fire or electrical hazard may result
causing property damage, personal injury or loss of life.
The air handler area must not be used as a broom closet or for any other
storage purposes, as a fire hazard may be created. Never store items
such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean-
ers or other cleaning tools.
2. Soap powders, bleaches, waxes or other Cleaning compounds;
plastic items or containers; gasoline, kerosene, cigarette lighter
fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the air handler with the blower door removed. To do so
could result in serious personal injury and/or equipment damage.
Improper installation, adjustment, alteration, or maintenance may cre-
ate a condition where the operation of the product could cause per-
sonal injury or property damage. Refer to this manual for assistance,
or for additional information, consult a qualified contractor, installer, or
service agency.
This product must be installed in strict compliance with the installation
instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical codes.
WARNING
!
WARNING
!
WARNING
!
CAUTION
!
ISO 9001
Certified Quality
Management System

Advertisement

Table of Contents
loading

Summary of Contents for York ME08B

  • Page 1: Table Of Contents

    INSTALLATION MANUAL STANDARD ECM MODULAR MULTI-POSITION AIR HANDLERS ISO 9001 Certified Quality MODELS: ME SERIES Management System LIST OF SECTIONS GENERAL ..........1 BLOWER SPEED CONNECTIONS .
  • Page 2: Safety

    5169034-UIM-B-0216 SAFETY REQUIREMENTS INSPECTION 1. Failure to carefully read and follow all instructions in this manual As soon as a unit is received, it should be inspected for possible dam- can result in air handler malfunction, death, personal injury and/or age during transit.
  • Page 3: Typical Installation

    5169034-UIM-B-0216 LOCATION Location is usually predetermined. Check with owner’s or dealer’s OUTER TIE PLATE (3 PLACES) installation plans. If location has not been decided, consider the following in choosing a suitable location: 1. Select a location with adequate structural support, space for service access, and clearance for air return and supply duct connections.
  • Page 4: Gasket Location

    A0327-001 FIGURE 5: Dimensions & Duct Connection Dimensions TABLE 1: Dimensions 1, 2 Dimensions Wiring Knockout Dimensions MODELS Height Width Bottom Opening Top Opening Power Control ME08B 21-1/2 17-1/2 16-1/2 16-1/2 ME12B 21-1/2 17-1/2 16-1/2 16-1/2 7/8 (1/2) ME14D 22-1/2...
  • Page 5: Duct Work And Connections

    5169034-UIM-B-0216 SECTION IV: DUCT WORK AND SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL RIGHT CONNECTIONS WARNING MIN. 3/8” THREADED ROD Use only 1/2” screws to connect duct work to bottom of unit. Air supply and return may be handled in one of several ways best suited to the installation.
  • Page 6: Electric Heater Installation

    5169034-UIM-B-0216 SECTION V: ELECTRIC HEATER INSTALLATION If the air handler requires electric heat, install the electric heat kit according to the installation instructions included with the kit. After installing the kit, mark the air handler nameplate to designate the heater kit that was installed.
  • Page 7: Standard Ecm

    5169034-UIM-B-0216 FIGURE 9: Line Power Connections SECTION VII: LOW VOLTAGE CONTROL The standard ECM motor operates when a 24 VAC signal is sent to any CONNECTIONS of its 5-speed taps. If simultaneous 24 VAC inputs are present, the motor operates at the highest speed tap that is energized. The lowest The 24 volt power supply is provided by an internally wired low voltage speed is 1, and the highest speed is 5.
  • Page 8: Physical And Electrical Data - Cooling Only

    5169034-UIM-B-0216 SECTION IX: UNIT DATA TABLE 2: Physical and Electrical Data - Cooling Only Models ME08B ME12B ME14D ME16C ME20D Blower - Diameter x Width 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10...
  • Page 9: Electric Heat Performance Data: 208/230-1-60 & 208/230-3-60

    Heater Heater Air Handler Models Min. Circuit Ampacity MOP. Amps @240V Models 208V 230V 208V 230V 6HK(0,1)6500206 14.9 16.1 6HK(0,1)6500506 25.8 28.0 ME08B 6HK(0,1)6500806 39.0 42.7 6HK(0,1)6501006 47.4 52.0 6HK(1,2)6501306 60.6 66.6 6HK(0,1)6500206 16.8 18.0 6HK(0,1)6500506 27.6 29.9 6HK(0,1)6500806 40.9 44.6...
  • Page 10: Electrical Data For Multi-Source Power Supply: 208/230-1-60

    TABLE 8: Electrical Data For Multi-source Power Supply: 208/230-1-60 Min. Circuit Ampacity MOP. Heater Heater 208V 230V 208V 230V Air Handler Amps Models Models Circuit Circuit @240V ME08B 6HK16501306 22.9 37.6 24.9 41.5 6HK16501306 24.8 37.6 26.8 41.5 6HK16501506 27.7 43.3 30.0 47.9...
  • Page 11: Electrical Data For Single Source Power Supply: 208/230-3-60

    TABLE 9: Electrical Data For Single Source Power Supply: 208/230-3-60 Field Wiring Heater Heater Air Handler Amps Min. Circuit Ampacity MOP. Models Models @240V 208V 230V 208V 230V ME08B 6HK36501025 23.1 28.3 30.9 6HK36501025 23.1 29.8 32.4 6HK36501525 34.6 42.2 46.2 ME12B 6HK36501825 41.6...
  • Page 12: Air Flow Data (Cfm)

    0.40 0.50 0.60 0.70 #5 HI #4 MED-HI CM18B #3 MED #2 MED-LO #1 LO #5 HI #4 MED-HI ME08B CM24B #3 MED #2 MED-LO #1 LO #5 HI #4 MED-HI CM30B #3 MED #2 MED-LO #1 LO #5 HI...
  • Page 13: Uim-B

    5169034-UIM-B-0216 TABLE 11: Air Flow Data (CFM) Blower External Static Pressure (in. wc.) Models CM Models Motor Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 #5 HI 1776 1735 1700 1657 1617 1577 1529 #4 MED-HI 1701 1663 1621 1583 1538 1497 1453...
  • Page 14: Maintenance

    5169034-UIM-B-0216 SECTION X: MAINTENANCE Drill 2 holes, one 12” away from the air handler in the supply air duct and on 12” away from the air handler in the return air duct (before any Filters must be cleaned or replaced when they become dirty. Inspect at elbows in the duct work).
  • Page 15: Wiring Diagram

    5169034-UIM-B-0216 SECTION XIII: WIRING DIAGRAM WHEN INSTALLING HEATER KIT, BE SURE THE BLOWER SPEED IS SEE INSTALLATION INSTRUCTIONS FOR PROPER SET TO THE SPEED SPECIFIED FOR THE AIR HANDLER/HEATER KIT LOW VOLTAGE FIELD WIRING CONNECTIONS. COMBINATION ON THIS UNIT'S INSTALLATION INSTRUCTIONS. HEATER KITS: 6HK*6500206 6HK*6500506...
  • Page 16: Wiring Diagram - Three Phase Heat Kits

    5169034-UIM-B-0216 3 PHASE ELECTRIC HEAT KITS BLUE RLY 3 BLACK HEATER KITS: BLUE 6HK36501025C RLY 2 HEATER KIT: 6HK36501525C RLY 6 RLY 3 6HK36501825C RLY 1 RLY 5 RLY 2 BLUE BLUE WHITE YELLOW BLUE YELLOW RED / WHITE PURPLE RLY 4 RLY 1 RED / WHITE...
  • Page 17: Start Up Sheet

    5169034-UIM-B-0216 SECTION XIV: START UP SHEET Residential Air Handler Print Form Reset Form with Electric Heat Start-Up Sheet Proper start-up is critical to customer comfort and equipment longevity Start-Up Date Company Name Start-Up Technician Owner Information Name Address Daytime Phone City State or Province Zip or Postal Code...
  • Page 18 Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Subject to change without notice. Published in U.S.A 5169034-UIM-B-0216 Copyright © 2016 by Johnson Controls, Inc. All rights reserved. Supersedes: 5169034-UIM-A-0216 York International Corp. 5005 York Drive Norman, OK 73069...