Upper Segment Assembly - York MCH CRAH Installation And Assembly Manual

Air handling units
Hide thumbs Also See for MCH CRAH:
Table of Contents

Advertisement

Form CRAH102.20-N1
Issue date: 03/11/2024

Upper segment assembly

Remove the discharge grate from
the top of the lower segment before
installing the top segment into position.
Figure 29: Discharge grate assembly
Table 9: Upper tier and lower tier specifications
Upper tier
Description
Part No.
005 07307 004 (one per unit)
Dimensions (in.) 49.1 (height) x 139 (width)
Wire
2 in. x 4 in. mesh, 11 GA wire
Finish
Black powder finish, no prime
Wire
0.12 in. diameter wire
Figure 30: Gasket installation (1)
Callout
Description
A
Install the gasket 1.0 in. thick x 1.0 in. wide across the top surface of the internal support rails
B
Install the gasket 1.8 in. thick x 2.25 in. wide to the top surface of the raceways around the entire perimeter of
the unit
C
Install the gasket 1.0 in. thick x 1.0 in. wide across the top surface of the drain pan flange
Johnson Controls
Section 3 - Handling, storage, and installation
The discharge grate from the top tier unit is installed to
the top of the bottom unit for shipment. Remove and
install the grate on the discharge of the top tier in the
field. See the following figure.
Lower tier
Description
Part No.
005 07307 003 (two per unit)
Dimensions (in.)
97.13 (height) x 139 (width)
Wire
2 in. x 4 in. mesh, 11 GA wire
Finish
Black powder finish, no prime
Wire
0.12 in. diameter wire
3