112702 – HIHI T-Exhaust A2 (abs)
Red alarm. Initiated by EMU.
Cause
Exhaust gas temperature of this
cylinder is too high.
112703 – HIHI T-Exhaust A3 (abs)
Red alarm. Initiated by EMU.
Cause
Exhaust gas temperature of this
cylinder is too high.
112704 – HIHI T-Exhaust A4 (abs)
Red alarm. Initiated by EMU.
Cause
Exhaust gas temperature of this
cylinder is too high.
112705 – HIHI T-Exhaust A5 (abs)
Red alarm. Initiated by EMU.
Cause
Exhaust gas temperature of this
cylinder is too high.
112706 – HIHI T-Exhaust A6 (abs)
Red alarm. Initiated by EMU.
Cause
Exhaust gas temperature of this
cylinder is too high.
112707 – HIHI T-Exhaust A7 (abs)
Red alarm. Initiated by EMU.
Cause
Exhaust gas temperature of this
cylinder is too high.
Corrective action
1. Check emission values (→ Page 47).
2. Check ignition timing (→ Page 176).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values (→ Page 47).
2. Check ignition timing(→ Page 176).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values (→ Page 47).
2. Check ignition timing (→ Page 176).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values (→ Page 47).
2. Check ignition timing (→ Page 176).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values (→ Page 47).
2. Check ignition timing (→ Page 176).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values (→ Page 47).
2. Check ignition timing (→ Page 176).
3. Check valve drive (exhaust valves do not close).
MS150121/02E 2017-09 | Troubleshooting | 75