1.4540.033 – Battery Volt High Error
Red alarm. Initiated by TecJet.
Cause
Supply voltage has reached
maximum limit value.
1.4540.034 – FGT High Limit Error
Red alarm. Initiated by TecJet.
Cause
Gas temperature before TecJet is
above the preset limit value.
1.4540.035 – Delta P High Limit Error
Red alarm. Initiated by TecJet.
Cause
Pressure difference through
TecJet above the preset limit
value.
1.4540.036 – FGP High Limit Error
Red alarm. Initiated by TecJet.
Cause
Gas pressure before TecJet is
above the preset limit value.
1.4540.037 – Watchdog Reset
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.038 – CAN Flow Demand Failed
Red alarm. Initiated by TecJet.
Cause
Position setpoint not received or
received too late.
1.4540.040 – TecJet Shutdown
Red alarm. Initiated by TecJet.
Cause
Summary alarm (for details, refer
to the source alarm).
Corrective action
1. Check supply voltage.
2. Check cabling (→ Page 202).
Corrective action
1. Check TecJet settings.
2. Check gas temperature.
Corrective action
1. Check TecJet settings.
2. Check gas pressure.
Corrective action
1. Check TecJet settings.
2. Check gas pressure.
Corrective action
u Restart TecJet.
Corrective action
1. Check TecJet setting.
2. Check cabling (→ Page 202).
Corrective action
u Rectify cause of alarm.