1.4540.026 – Analog Input Low Error
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
1.4540.027 – Analog Input High Error
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
1.4540.028 – PWM Duty Cycle Low Error
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
1.4540.029 – Battery Volt Low Error
Red alarm. Initiated by TecJet.
Cause
Supply voltage has reached
minimum limit value.
1.4540.030 – FGT Low Limit Error
Red alarm. Initiated by TecJet.
Cause
Gas temperature before TecJet is
below the preset limit value.
1.4540.031 – Delta P Low Limit Error
Red alarm. Initiated by TecJet.
Cause
Pressure difference through
TecJet below the preset limit
value.
1.4540.032 – FGP Low Limit Error
Red alarm. Initiated by TecJet.
Cause
Gas pressure before TecJet is
below the preset limit value.
114 | Troubleshooting | MS150121/02E 2017-09
Corrective action
u Check TecJet setting.
Corrective action
u Check TecJet setting.
Corrective action
u Check TecJet setting.
Corrective action
1. Check supply voltage.
2. Check cabling (→ Page 202).
Corrective action
1. Check TecJet settings.
2. Check gas temperature.
Corrective action
1. Check TecJet settings.
2. Check TecJet installation direction.
Corrective action
1. Check TecJet settings.
2. Check gas pressure.