Page 1
Vertiv™ Liebert® APM Plus User Manual 50-500 kVA UPS...
Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Where conductive dust, corrosive gases, salts, or flammable gases are present • Near heat sources or strong electromagnetic interferences. Disclaimer Vertiv disclaims any and all responsibility or liability for the defects or malfunction caused by: • Application range or operating environment outside the specifications •...
Page 10
IEC/EN/BS 62040-2:2018 Additional information regarding adherence to these directives and regulations is included in the appendices NSR and EMC to the Declarations of Conformity. If needed, the Declarations of Conformity can be requested to Vertiv. 2011/65/EU Directive of the council for adapting the legal regulations of member states on the restriction of the use of certain hazardous substances that can be used in the manufacture of electrical and electronic equipment.
Page 12
WARNING! The user must select an appropriate MCCB to protect against short circuit and overload for the battery. We recommend using Vertiv BCB box to provide a better solution. WARNING! The power cables must be routed in the metal cable trough in order to avoid cable damage and reduce the electromagnetic radiation.
Page 20
In case of inverter failure and output fuse blowout, the load will automatically transfer to the bypass, and the output power supply will not be interrupted. In this situation, please contact the local customer service center of Vertiv for technical support.
Page 26
EOD voltage, if the mains is recovered, the UPS will restart automatically after a certain time of delay. This function and the automatic restart type can be set by the service engineer authorized by Vertiv. During the process of automatic restart time of delay, the UPS will charge the battery to protect against the power-off risk of the load device caused by mains power failure.
9. Maximum boost charge protection time To protect against the battery overcharge damage caused by long time boost charge, a protect time setting is essential. The limit of time setting shall be configured by service engineer through the Vertiv software setting. 2 Overview...
20%, the automatic discharge cannot be executed. The periodic interval can be set from 30 to 360 days. The battery maintenance test function can be disabled through the Vertiv software setting. Conditions: Battery at float charge for at least 5 h, load equal to 20% to 100% of rated UPS capacity.
(which charges the battery) will be reduced correspondingly to provide optimal charging voltage for the battery, thus prolonging the battery service life time. This function must be used together with the Vertiv battery temperature detection device (a standard option). 2.6 Battery Protection WARNING! The user must select an appropriate MCCB to protect against short circuit and overload for the battery.
2. Unpack the UPS and battery under the guidance of authorized service engineer. Visually inspect whether the UPS and battery have any transportation damage. If there is any damage, report to the carrier or Vertiv representative immediately. 3. Verify the UPS label and confirm the correctness of the UPS. The UPS label is attached on the back of the door.
This simple, dynamic display speeds operator response to changing power input and demand. Many of the settings will depend on the UPS type and features. Many other settings will be made during the UPS setup by Vertiv Tech service personnel.
Service--All functions of Administrator and the permission to alter system configuration, choose serial communication protocol, enable equalize battery charging and change Service PIN; PIN required. Vertiv Tech Liebert Services sets PINs when setting up the UPS. These default PINs may be changed by those with Administrator or Service access (see above).
Page 111
NOTE: If the alarm is caused through setting the software value by Vertiv authorized engineer, and you wish to change the setting values, please contact the Vertiv local customer service center.
At the moment, the system is powered on, and the startup screen pops up. 3. If ECO mode is required, contact Vertiv service engineer to set it through the setting software. If you wish to set it by yourself, you can enable it through the sub-menu under 'SETUP' on the TOUCHSCREEN screen. For details, refer to Operator Controls.
Periodical self-test is to test the battery activity. The periodical self-test is regular, and the self-test period can be configured via the Vertiv software setting. During the periodical self-test, if the battery maintenance requirement is met, the system will generate audible/visual alarm and corresponding records. The periodical self-test does not update the battery curve table.
During the automatic recovery delay, the UPS will charge its batteries to provide a safety margin for equipment shutdown if input power fails again. NOTE: During the automatic restart process, manual startup is disabled. Automatic restart must be set by Vertiv's authorized service engineer through Vertiv setting software.
IMPORTANT! Users must choose appropriate switching devices to protect the battery from short circuit and overload, etc. We recommend using the Vertiv BCB to provide a more perfect solution. The battery is connected to the UPS through the BCB. The BCB is manually closed and has an electronic tripping device controlled by the UPS control circuit.
Vertiv™ Liebert® APM Plus User Manual 7.12 Battery Temperature Sensor (Optional) Vertiv provides an optional battery temperature sensor which can measure the temperature about four positions. When using multiple battery temperature sensors, the monitor selects the highest temperature detected among them for display. The...
Region Vertiv provides an optional battery ground fault detector. It includes a mutual inductor and a PCB, which should be installed in the BCB cabinet. If the BCB cabinet uses top cable entry, the mutual inductor should be installed on the inside of the top plate of the BCB cabinet;...
WARNING! To achieve coordinated operation of the modules in the parallel system, it is required to configure each module separately using Vertiv software setting. This must be done by Vertiv service personnel. 8.2.2 Cabinet Installation Place the UPS modules side by side and interconnect as shown in Figure 8.1 on the next page.
8.3.3 Procedures for Isolating One UPS module from Parallel System IMPORTANT! These procedures shall only be carried out by service personnel of Vertiv or under their guidance. WARNING! After isolating one UPS module, when the parallel system is not overload, then proceed with steps below.
Seismic anchor Fix the UPS onto the concrete floor. WARNING! Only Vertiv authorized engineers shall carry out the installation. WARNING! Carry out the installation strictly following the instructions. Failure to observe this could cause personnel injury or damage to the UPS and seismic anchor kits.
10.1 SNMP Protocol Communication If you need to monitor the UPS through network, you may select the UNITY card or SIC card provided by Vertiv. These two cards support SNMP protocol. Both the UNITY card and SIC card are network management cards which make the UPS an IOT device.
Disposal of battery waste as per local regulations. In India, dispose to authorized recyclers as mentioned under current E- waste act/rules of the relevant state pollution control board. List of authorized recyclers are available on the relevant website of state pollution. Vertiv has list of collection centre for e-waste available at below mentioned site: https://www.vertiv.com/en-in/about/e-waste-management/ Packing waste: Disposal of battery waste as per local regulations.