LCD OPERATION GUIDE (continued)
Item
Audible Alarm
Menu / Outlet Control
Use this menu to configure UPS outlet performance. Outlets are divided into Critical (CL) and Non-Critical (NCL)
outlets. Connect the mission critical devices into Critical outlets and nonessential equipment into NCL outlets. If
equipment needs to be shut down or reboot in a specific order, plug the equipment into separate outlet groups.
Enter the submenu "Config UPS" to configure the total output of the UPS, including CL and NCL outlets. Enter "Config
NCL" if you want to have additional settings for NCL outlets, for example, cut off the power provision to the
nonessential equipment during a blackout to reserve runtime for mission critical devices.
Please note that settings configured in the "Config UPS" submenu take precedence over those in "Config NCL" for the
same function. For instance, if "Uptime on Battery" is set to "Enable: 300 seconds" in the "Config UPS" submenu and
"Enable: 600 seconds" in the "Config NCL" submenu, the UPS will cut off all power output, including both CL and NCL
outlets, after running on battery mode for 300 seconds.
Submenu / Config UPS
Item
Delay Turn On
Delay Turn Off
Reboot Duration
Minimum Restored
Capacity
Uptime on Battery
Reserved Runtime
Default
Normal
Quiet
Quiet
Mute on Battery
Off
Default
4 seconds
0-600 seconds
4 seconds
0-600 seconds
12 seconds
4-300 seconds
0%
0-100%
Enable: 5-1800
seconds
Disable
Disable
Enable: 0-1800
seconds
Disable
Disable
Option
Normal contains fault and warning alarms and all
reminding alarms of battery operation including
switching to battery power, working under battery
mode, reaching Low Battery Threshold, soon
running out of battery, and Low Battery
Shutdown.
If Quiet is selected, the UPS will emit fault and
warning alarms and reminding alarm indicating
the UPS reaches Low Battery Threshold.
If Mute On Battery is selected, only fault and
warning alarm will sound.
All alarms are disabled if Off is selected.
Option
The amount of time that the outlets will wait
before actual startup.
The amount of time that the outlets will wait
before actual shutdown.
The amount of time that the outlets will remain off
before the UPS restarts itself.
It is the criteria for UPS to perform auto-restart as
utility is restored. If battery capacity is higher than
this setting, the auto-restart will be performed;
otherwise, the UPS will keep charging the battery
until battery capacity reaches that level.
Set the maximum runtime on battery mode. The
UPS will shut down after the amount of time spent
in battery mode has reached this setting. Make
sure the estimated runtime is larger than this
setting; otherwise, the UPS will still stop supplying
power when it is running out of battery.
When the UPS is in battery mode, it will cut off
output power when the remaining runtime
reaches the level.
12