Lamborghini Caloreclima ALHENA C Instructions For Use, Installation And Maintenance page 272

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 236
power levels "Hi","ME" and "Lo" can be scrolled by pressing the "Heating + or -" buttons to
recheck or correct the CO
• Press the "OFF/Summer/Winter" and "Heating +" buttons for 5 seconds to exit the complete
manual calibration mode and save the settings. Modifying the parameters for adjusting the CO
in complete manual calibration mode takes not more than about 8 minutes.
TEST mode activation
Do a heating or DHW request.
Press the heating buttons (details 3 and 4 - fig. 1) for 5 seconds to activate TEST mode. After igni-
tion, the boiler adjusts to maximum heating power (parameter P41 defines the maximum heating
power and changes according to the selected boiler model).
The Heating and DHW symbols (fig. 45) flash on the display and the set power will appear.
Press the heating buttons (details 3 and 4 - fig. 1) to increase or decrease the power (Mini-
mum=0%, Maximum=100%).
By pressing the DHW "-" button (detail 1 - fig. 1), boiler output is immediately adjusted to mini-
mum (0%).
Wait about 1 minute for stabilisation.
By pressing the DHW "+" button (detail 2 - fig. 1), boiler output is immediately adjusted to maxi-
mum (100%).
If the TEST mode is activated and enough hot water is drawn to activate the DHW mode, the boiler
remains in TEST mode but the 3-way valve goes to DHW.
To deactivate the TEST mode, press the heating buttons simultaneously (details 3 and 4 - fig. 1)
for 5 seconds.
The TEST mode is automatically disabled in any case after 15 minutes or on stopping of hot water
drawing (if enough hot water is drawn to activate DHW mode).
Heating power adjustment in TEST mode
To adjust the heating power (in addition to parameter P41 modification) put the boiler in TEST mo-
de. Press the "heating + or -" buttons to increase or decrease the power. Press the reset button
for 1 second within 20 seconds after the modification and the maximum power will remain that just
set (settable range 0 ÷ 95). Exit TEST mode.
272
EN
value.
2
fig. 45- TEST mode (heating power = 100%)
cod. 3540000251 - Rev. 00 - 03/2024
ALHENA C
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alhena 24 cAlhena 28 cAlhena 34 c

Table of Contents