the three power levels "Hi", "ME" and "Lo" can be scrolled by pressing the "Heating + or -
" buttons to recheck or correct the CO
• Press the "OFF/Summer/Winter" and "Heating +" buttons for 5 seconds to exit the com-
plete manual calibration mode and save the settings. Modification of the parameters to
adjust the CO
Checking the combustion values
MAKE SURE THE FRONT PANEL IS CLOSED AND THE INTAKE/FUME EXHAUST DUCTS
ARE COMPLETELY ASSEMBLED.
1. Put the boiler in heating or DHW mode for at least 2 minutes.
2. Activate TEST mode (see *** 'TEST mode activation' on page 272 ***).
3. Using a combustion analyzer, connected to the arrangements located on the starting accesso-
ries on top of the boiler, check that the CO
maximum and minimum power, matches that given in table 9.
Table 9- CO2 values to respect
G20
G30/G31
9% ±0,8
4. If the combustion values do not match, do the manual calibration as described in the following
paragraph.
5. Activate a manual calibration and then modify the Hi, ME and Lo values to obtain values of
CO
as per table 9.
2
THE "CO" VALUES PRODUCED BY THE DEVICE COMPLY WITH LOCAL REGULATIONS.
Calibration
IMPORTANT: During the "Complete ma-
nual calibration" or "Manual calibration"
procedure, or during the "CO
Manual calibration
Calibration procedure.
• Put the boiler in standby mode.
• To activate manual calibration, simultaneously press the OFF/Summer/Winter buttons (detail
7 - fig. 1) and the "Heating +" button (detail 4 - fig. 1) for 5 seconds. Calibration will start in
heating request. If there is insufficient heat dissipation, a DHW request can be made (the three-
way valve will automatically switch in the DHW circuit).
• Manual calibration will start. During the ignition phase, the flashing symbols MA and "nu"+ ra-
diator + faucet alternating will appear. With flame present (flashing icons "Hi + flame + faucet
+ radiator") the boiler will do the check first in Hi (maximum power) then ME (Medium power)
then Lo (minimum power). Calibration can be stopped at any time by pressing the "OFF/Sum-
mer/Winter" and "Heating +" buttons for 5 seconds.
• Afterwards, a numerical value between 0 and 6 will appear on the display (at this point the
boiler is at minimum power "Lo"). At this point the CO
Using the "DHW + and -" buttons, adjust the CO
+ or -" buttons are pressed, the display will show the modified value and then the icon "Lo" (to
indicate the minimum power level). The adjustment range is from 0 to 6 (in all power levels Hi,
ME, Lo), increasing the value will increase the CO
Press the "Heating +" button, the display will show the icon "ME", a numerical value will appear
when the ignition/intermediate power is reached. Using the "DHW + and -" buttons, adjust the
CO
at medium/ignition power ME; each time the "DHW + or -" buttons are pressed, the di-
2
splay will show the modified value and then the icon "ME" (to indicate medium/ignition power
level). Press the "Heating +" button, the icon "Hi" will appear on the display and a numerical
value will appear when the maximum power is reached.
Using the "DHW + and -" buttons adjust the CO
270
EN
in complete manual calibration mode will take not more than about 8 minutes
2
G230
10% ±1
10% ±1
value che-
2
cod. 3540000251 - Rev. 00 - 03/2024
level.
2
content in the fumes, with the boiler operating at
2
cking" phase, the front panel must be
closed and the inlet/fume outlet ducts
completely assembled.
can be adjusted.
2
at minimum power (Lo); each time the "DHW
2
level and vice versa.
2
at maximum power (Hi).
2