MALFUNCTIONING
The appliance loses water during
heating function.
Dew formations are present on the
front panel.
A few water drops are present on
the air outlet flap.
The appliance loses water during
cooling only function.
The appliance emits excessive
noise.
Do not try to repair the appliance by yourself.
If the problem has not been solved, please contact your local retailer or the closest
assistance service. Supply detailed information about the malfunction and the equip-
ment version.
EN - 40
CAUSE
-
Losses in the water connection
of the system.
-
Losses in the valves unit.
-
The thermostatic valve inte-
grated in the connection unit
between panel and battery does
not close flow towards the wall.
-
Thermal insulators are discon-
nected.
-
In situations of high relative
ambient humidity (>60%) con-
densation phenomenons may
occur, especially at minimum
ventilation speeds.
-
The condensation basin is
clogged.
-
The condensation drain has not
the necessary inclination for cor-
rect drainage.
-
The connection pipelines and
the valves unit are not insulated
correctly.
-
The fan touches the structure.
-
The fan is unbalanced.
WHAT MUST BE DONE?
-
Check the loss and firmly tighten
the connections.
-
Check the status of the seals.
-
Replace the junction which inte-
grates the thermostatic valve in
the water inlet upper unit.
-
Check for correct positioning of
the thermoacoustic insulators,
paying particular attention to the
front one above the finned bat-
tery.
-
Once relative humidity drops,
the phenomenon disappears.
In any case, the possible fall
of some water drops inside the
appliance does not indicate a
malfunction.
-
Slowly pour a water bottle in
the bottom part of the battery to
ensure drainage; if necessary,
clean the basin and/or improve
inclination of the drain pipe.
-
Check for insulation of the pipe-
lines.
-
Check for possible interferences
by manually rotating the fan.
-
Unbalancing determines exces-
sive vibrations of the machine:
replace the fan.