It is not possible to connect the parallel input the one of other
circuit boards; use separate contacts.
To connect the presence sensor, it is necessary to use a double-insulated cable with
a minimum section of 2x0,5 mm2 and maximum length of 20 m. Keep this connection
separated from the power supply line of the appliance.
5.1.2 - Hot/cold generator switching on consent contact
The screw connector (C) on the black and grey cables of the thermoelectric head is a
free contact (closed = valve open, 230 V max, 1 A max) to give consent for switching
on of the hot/cold generator.
5.2 - CONNECTION WITH WIRED REMOTE CONTROL B0736 OR
THIRD PARTIES MODBUS
Connect the cables coming from the "A B" connection
-
of the B0736 command with the respective wires on
the mammoth connected to the panel lid, taking care
to respect the polarity, yellow cord "A" and orange cord
"B", connecting the farthest unit with the 120 Ohm
resistor supplied with the appliance.
-
Enable Remote configuration (paragraph "5.4", con-
figuration parameter "CF").
-
All the commands "
abled and the message "rE" will appear on the display
every time they are activated.
-
The indicator "
ation, the indicators "
the set fan speeds.
-
As regards the functionalities and settings, see the instructions of command
B0736.
5.3 - CONNECTION WITH SIOS CONTROL
Connect the cables coming from the "A B" connection of SIOS CONTROL with
-
the respective wires on the mammoth connected to the panel lid, taking care
to respect the polarity, connecting the farthest unit with the 120 Ohm resistor
supplied with the appliance.
" shows the chosen mode of oper-
", "A", "
" and "
" shall be dis-
" and
Bi2 WALL TR 1000/1200/1400
EN - 23