Huawei SmartLi 3.0 User Manual page 117

Hide thumbs Also See for SmartLi 3.0:
Table of Contents

Advertisement

SmartLi 3.0
User Manual (Long-Term Backup Power)
No.
Check Item
4
Installation
position
5
Ambient
temperature
6
Ambient
humidity
Table 7-2 Product components
No.
Check Item
1
Cabinet
appearance
2
Battery
appearance
Issue 09 (2024-01-31)
Acceptance Criteria
There is no air exhaust
vent or refrigerant copper
pipe of the air conditioner
placed above the lithium
battery cabinet, and no
other water leakage risks
exist.
Actual temperature: ______
°C (Allowed temperature:
0°C to 40°C; recommended
temperature: 20°C to 25°C)
Actual humidity: ______%
RH (5%–95% RH, non-
condensing)
Acceptance Criteria
The cabinet is free from
dust (on air filters and
fans), rust, and
deformation.
● Batteries are free from
stains.
● Battery wiring terminals
are intact.
● Batteries are intact and
free of damage,
deformation, bulges,
and cracks.
● Batteries have no
electrolyte leakage. (If
electrolyte leakage
occurs, there will be a
pungent smell.)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting: Rectify
the fault based on the
acceptance criteria.
● Check method: Measure
using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
● Check method: Measure
using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting: Rectify
the fault based on the
acceptance criteria.
● Check method: visual
inspection
● Troubleshooting:
Contact technical
support.
7 Maintenance
Check Interval
Monthly
Monthly
Monthly
Check Interval
Monthly
Monthly
109

Advertisement

Table of Contents
loading

Table of Contents