Prosonic M FMU 40/41/43 with HART and 4 ... 20 mA
5.10
Resetting an interference echo suppression (tank

map)

It is always advisable to reset the interference echo suppression (tank mapping) when:
• a device with an unknown history is used
• an incorrect suppression was input.
Proceed as follows:
1.
Switch to the "extended calibr." (05) function group and to the "selection" (050)
function.
2.
Select "extended map."
3.
Then proceed to the "cust. tank map" (055) function.
4.
Select
– "reset", to delete (reset) the existing interference echo suppression.
– "inactive" to deactivate an existing interference echo suppression. The
suppression remains saved.
– "active" to reactivate an existing interference echo suppression.