20. Care

It is essential that the humidifier is easy to inspect and easily accessible on site.
Prior to opening the humidifier, it must be disconnected from the electricity and water supply.
Then unscrew the cover screws and remove the cover. In case of pollution, the fluid tank of the humidifier
must be cleaned by using a clean, medium hard brush and clean water. The transducers must be wiped
clean with a soft, scratch-free cloth. Incrustations or solid deposits on the transducers must be carefully
removed. For that purpose, it is recommended to use 20% formic acid.
The finger guard of the radial fan with the inner fleece is removable. The fleece can be cleaned in a warm
washing solution.
The care intervals depend on the respective degree of contamination of the humidifier. It depends directly on
the cleanliness of the intake air and the feed water quality. It may be necessary to perform care at shorter
intervals.
For better filtering of extremely polluted intake air, an additional filter box is recommended (see optional
accessories).
The performance of the ultrasonic transducers decreases with actual operating hours. The life time of the
ultrasonic transducers will be shortened by unfavourable operating conditions e.g. water and air pollution or
overvoltage.
[MBA_UB-1...4-CT_3.1_EN] Rev.: 02/2022 Translation of the original instructions
No liability accepted for translation or printing errors. Subject to changes in dimensions, weights and other technical data.
All rights reserved. Modifications, reprints and photomechanical reproduction, even in extract from, require the express perm ission of BOGA GmbH, Werkstraße 16, D-59494 Soest.
Good accessibility and exchangeability of the humidifier save costs!
Deposits are a direct consequence of inadequate water quality!