10. Hydraulic connection

10.1 Hydraulic conditions

Fig. 9 - Schematic diagram
Definitions
1. UB-4/CT/3.1
2. Stop cock (included in the scope of delivery)
3. Demineralised water:
1 bar < pressure ≤ 4 bar
5 µS/cm < conductivity ≤ 20 µS/cm
4. Water demineralisation system (reverse osmosis system)
5. Drinking water supply (on site)
6. Concentrate
7. Water supply for plastic tube Ø 6 mm
8. Water overflow for plastic tube Ø 12 mm
9. Water discharge for plastic tube Ø 12 mm
10. Water overflow hose
11. Free discharge according to DIN 1988-100 (on site)
Important notes:
The humidifier may be operated with fully demineralised water only (produced for example by a
reverse osmosis system). The demineralised water must have a conductivity of min. 5 µS/cm
and max. 20 µS/cm.
The contamination of drinking water may not exceed the max. values laid out in the drinking
water regulations.
The demineralised water is corrosive, therefore use stainless steel or plastic only. Non-ferrous
metals (e.g. copper, brass) must not be used.
Water pressure must be minimum 1 bar and maximum 4 bar.
The drainage system on site must be set in accordance with DIN 1988-100.
The water overflow- and discharge hose must be laid with a constant slope of min. 3% (3 cm on
1 m) to the free discharge.
For easy revision, the stop cock included in the delivery must be installed in the demineralised
water supply line close to the device.
16
No liability accepted for translation or printing errors. Subject to changes in dimensions, weights and other technical data.
All rights reserved. Modifications, reprints and photomechanical reproduction, even in extract from, require the express permission of BOGA GmbH, Werkstraße 16, D-59494 Soest.
of hydraulic conditions
All materials coming into contact with the demineralised water must be resistant
to demineralised water (observe pressure and temperature resistance).
Demineralised water pipes must be flushed prior to starting the device.