9. Aerosol distribution systems

Basic conditions:
1.
The humidifier must always be operated with an external aerosol distribution system (tube/pipe).
2.
Aerosol distribution may not be done in such a way that the device sucks the aerosols in again through
the built-in axial fan and thus works in the aerosol short circuit. As a result, the device could be damaged.
3.
For aerosol distribution, all pipes/tubes must be equally long.
9.1

Aerosol Jet

The aerosol jet must
always be inclined
towards the conden-
sate drain
Condensate drain
to the drainage
The flexible tubes may be connected to the aerosol jet as shown in Fig. 5 in accordance with variants
a)
or b). The optimal solution would be a). In that case, aerosol density is the same along the length
of the aerosol jet whereas in
aerosol jet.
from the
humidifier
Fig. 6 - Cross-section of aerosol jet
14
No liability accepted for translation or printing errors. Subject to changes in dimensions, weights and other technical data.
All rights reserved. Modifications, reprints and photomechanical reproduction, even in extract from, require the express permission of BOGA GmbH, Werkstraße 16, D-59494 Soest.
> 0°
Variante a)
Ø 40 mm
Fig. 5 - Aerosol Jet
b)
the aerosol density decreases nearly linearly towards the end of the
Variante b)
Difference in height "h" as low
as possible. The lower "h", the
higher the humidity output at the
openings of the aerosol jet.
Attention:
Aerosol jet holes
are burr-free!
Aerosol mist
The angle between
the aerosol inlet and
outlet must always
be > 90°
[MBA_UB-1...4-CT_3.1_EN] Rev.: 02/2022 Translation of the original instructions