13.4 Settings

AquaDrain Duration:
The AquaDrain duration is the time the humidifier needs to empty the fluid tray. This value is given
by design and depends on the type of humidifier, the size of the fluid tray and the installation.
Possible settings:
Default setting:
AquaDrain Cycle Time
The AquaDrain cycle time is directly linked to the automatic emptying of the fluid tray. The AquaDrain
process is also performed when there is a humidification request.
Possible settings:
Default setting:
AquaDrain Delay
The AquaDrain delay is used when several humidifiers are mounted in a system and AquaDrain is
enabled. The AquaDrain delay prevents all humidifiers from being emptied at the same time.
Possible settings:
Default setting:
Flush Time
The flushing time is the time at which the water supply line is flushed before the first operation and
after a certain period of inactivity.
Possible settings:
Default setting:
Inactivity Flush Timeout
If no humidification is requested, the humidifier is in standby mode. If the fluid tank is still filled, it is
automatically emptied after the adjustable time "Inactivity Drain Timeout"..
Possible settings:
Default setting:
[MBA_UB-1...4-CT_3.1_EN] Rev.: 02/2022 Translation of the original instructions
No liability accepted for translation or printing errors. Subject to changes in dimensions, weights and other technical data.
All rights reserved. Modifications, reprints and photomechanical reproduction, even in extract from, require the express perm ission of BOGA GmbH, Werkstraße 16, D-59494 Soest.
30 seconds, 1 minute, 2 minutes, 3 minutes, 4 minutes,
5 minutes, 6 minutes.
3 minutes
Disabled, 10 minutes, 30 minutes, 1,5 hours, 3 hours,
6 hours, 12 hours, 24 hours, 48 hours.
12 hours
No delay, 1x 15 minutes, 2x 15 minutes,
3x 15 minutes, 4x 15 minutes, 5x 15 minutes, 6x 15 minutes,
7x 15 minutes
No delay
15 seconds, 30 seconds, 120 seconds, 200 seconds
30 seconds
Default setting, 10 minutes, 30 minutes, 1,5 minutes, 3 hours,
6 hours,12 hours, 24 hours, 48 hours.
12 hours