Automatic Functions; Make Applied Settings - Boga AIRWIN UB-1 4/CT/3.1 Series Installation And Operating Instructions Manual

Ultrasonic universal humidifier
Table of Contents

Advertisement

15.2 Automatic functions

Flushing of water supply line:
The solenoid valve supply of the humidifier opens. The solenoid valve drain is open. The water
supply line is flushed without the fluid tank of the humidifier being filled.
The solenoid valve supply closes. The solenoid valve drain stays open for 180 seconds.
Filling the fluid tank:
The solenoid valve drain closes. The solenoid valve supply opens. The fluid tank of the
humidifier is filled. The water level is automatically controlled within narrow tolerances. Internal
safety monitoring of the water temperature and dry running protection is done automatically.
Humidification:
Once the maximum water level is reached and the humidification request is still present,
humidification will start.

15.3 Make applied settings

Adjust set point value for humidity.
Commissioning of the humidifier is completed.
[MBA_UB-1...4-CT_3.1_EN] Rev.: 02/2022 Translation of the original instructions
No liability accepted for translation or printing errors. Subject to changes in dimensions, weights and other technical data.
All rights reserved. Modifications, reprints and photomechanical reproduction, even in extract from, require the express perm ission of BOGA GmbH, Werkstraße 16, D-59494 Soest.
The feature "Flushing of water supply line" does not replace flushing of the
newly established water inlet pipe. Flushing only changes the demineralised
water (which may be hygienically questionable) in the supply line.
The fluid tank may only be filled if a humidification request has been made.
Otherwise the fluid tank of the humidifier will remain dry.
Fig. 41 - Continuous controller CT1
41