Structure And Functions Of The Control Board Airwin 3.1; Connections - Boga AIRWIN UB-1 4/CT/3.1 Series Installation And Operating Instructions Manual

Ultrasonic universal humidifier
Table of Contents

Advertisement

13. Structure and functions of the control board AIRWIN 3.1

13.1 Connections

Inputs
X9 - Connection of float switch:
1: Float switch, level "S1" black
2: Float switch, level "S1" brown
3: Float switch, level "S1" blue
4: Float switch, level "S1" grey
Notice:
Only connections relevant
to the device are shown.
1 2 3 4
X2
Fig. 24 - Control board PCB AIRWIN 3.1 Input
X2 - Connection to supply:
1: Power supply L 48 V-AC
2: Power supply N 48 V-AC
3: Release 48 V-AC, 24 V-DC
4: Release 48 V-AC, 24 V-DC
[MBA_UB-1...4-CT_3.1_EN] Rev.: 02/2022 Translation of the original instructions
No liability accepted for translation or printing errors. Subject to changes in dimensions, weights and other technical data.
All rights reserved. Modifications, reprints and photomechanical reproduction, even in extract from, require the express perm ission of BOGA GmbH, Werkstraße 16, D-59494 Soest.
5: Float switch, level "S2" black
6: Float switch, level "S2" brown
7: Float switch, level "S2" blue
8: Float switch, level "S2" grey
X9
1 2 3 4 5 6 7
8
1 2 3 4
X4
X4 - Connection hyg:
1: Hygrostat input 1
2: Hygrostat input 1
3: Hygrostat input 2
4: Hygrostat input 2
X8 - Connection sensor:
1: Current measurement -
2: Current measurement +
X8
1 2 3 4
X5
X5: - Connection Reg:
1: Control signal mA + (Ri: 500 Ω)
2: Control signal mA -
3: Control signal V + (Ri: 50 kΩ)
4: Control signal V -
1 2
25

Advertisement

Table of Contents
loading

Table of Contents